Installation and start-up of UPS B9000FXS
Installazione e avviamento B9000FXS
OMD10013 REV. I
39
11 INVERTER
START
WAIT PLEASE
The modulation of the inverter bridge is
started. The AC voltage reaches the
nominal value. The microprocessor
checks the synchronization with the
bypass line.
12
START UP FROM
MBCB
MOVE BYP - SWITCH
Move the selector
“NORMAL-BYPASS”
to NORMAL
The load is transferred to the inverter.
Led #5 lit green.
13
START UP END
WAIT PLEASE
The microprocessor checks that all the
output parameters (voltage, current,
frequency) are within the tolerance limits.
14 UPS
MODEL
OUTPUT VOLTAGE
Содержание ASD10