Installation and start-up of UPS B9000FXS
Installazione e avviamento B9000FXS
36
OMD10081 REV. I
5.4 SHUT-DOWN
PROCEDURE
No.
ACTION
LCD DISPLAY
OPERATING CHECKS
1
Open OCB
A30 GENERAL ALARM
The supply to the load is interrupted.
LED #7 off.
2
Open BCB
A30 GENERAL ALARM
The battery is disconnected from the
rectifier. Led #4 red flashing.
3
Open SBCB
A30 GENERAL ALARM
The bypass supply is disconnected. LED
#2 off.
4
Open RCB
A30 GENERAL ALARM
Rectifier and inverter shutdown.
5
BLANK
End of shutdown procedure.