Installation and start-up of UPS B9000FXS
Installazione e avviamento B9000FXS
OMD10013 REV. I
29
4.4
CONNECTION OF AUXILIARY CABLES
The UPS systems of the B9000FXS line can be connected to external controls/components
specifically designed to improve the safety and reliability of the device.
External manual bypass;
Diesel generator;
Auxiliary battery contact;
Remote emergency power off button (EPO).
The auxiliary cables are connected using a special terminal board placed aligned with the
power terminal boards.
The section of the terminals used is 6 mm
2
.
Picture 7 – Position of auxiliary terminals of B9000FXS