Installation and start-up of UPS B9000FXS
Installazione e avviamento B9000FXS
OMD10013 REV. I
13
2.3.7 Maintenance
Service and repairs must be carried out by skilled and authorized personnel. Before carrying
out any maintenance operation, UPS B9000FXS must be disconnected from AC and DC supply
sources.
The device is provided with internal isolators which allow to isolate the internal power circuits.
However the voltages of the supply sources are present on the terminals. To isolate the device
completely, provide external circuit breakers on the lines.
The device contains dangerous voltages even after shutdown and disconnection from the
supply sources, due to the internal capacitors which discharge slowly. Thus we recommend to
wait at least 5 minutes before opening the device doors.
Injury hazard due to electric shock!
Any operation must be carried out only when voltage is absent and in compliance
with safety directives.
Make sure the battery circuit breaker that may be placed near the battery has
been opened.
Isolate the device completely by operating the external circuit breakers.
Wait at least 5 minutes in order to allow the capacitors to discharge.
After switching off and disconnecting the device there still might be very hot components
(magnetic parts, heat sinks); therefore we recommend to use protective gloves.
High temperature of components
It is strongly recommended to use protective gloves due to the high temperatures that
may be reached during the operation.
Содержание ASD10
Страница 1: ...OPERATING MANUAL UPS MANUALE OPERATIVO UPS B9000FXS 60 80 100 125 160kVA ...
Страница 2: ......
Страница 5: ...Warnings and general information Avvertenze e informazioni generali 2 OMD10080 REV B ...
Страница 6: ...Warnings and general information Avvertenze e informazioni generali OMD10080 REV B 3 ENGLISH LANGUAGE ...
Страница 12: ...Warnings and general information Avvertenze e informazioni generali OMD10080 REV B 9 LINGUA ITALIANA ...
Страница 96: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 5 ENGLISH LANGUAGE ...
Страница 142: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 51 LINGUA ITALIANA ...