11/17
Operating Instructions AEC
51
Provide proper equipotential bonding within the system or plant. Plant components such as electrical
cabinets, control panels, machine frames must be connected by means of PE cables, i.e. sufficient
area and with good conductivity.
The shield of the control cables is to be connected to ground potential properly, i.e. with good
conductivity, on both sides (shield clamp). Mount shield clamps for cable shields close to the unit.
Connect the AEC and its components to an earthing point via short cables.
Excessive cable length and loosely suspended cabling must be avoided.
Contactors, relays and solenoids in the electrical cabinet are to be provided with suitable interference
suppression components.
Separate installation of power cables (AC and DC) and control cables is required.
Cables with a length >300 mm must be shielded, the cable shield must be connected to the mounting
plate on both sides. Use twisted cables where possible.
8.2
Conductor cross-section
The cable dimensions must be selected according to the current load and voltage drop to be
expected.
Select the cable cross-section of the cables such that the voltage drop is as small as possible.
Comply with any additional national and application-specific regulations and the separate UL
instructions.
The mains fuses and cable cross-sections are to be selected according to DIN VDE 0100 Part 430 and
DIN VDE 0298 Part 4 for the nominal operating point of the mains unit.
According to UL/CSA, approved Class 1 copper lines with a temperature range of 60/75 °C and
matching mains fuses are to be used for the power cables.
Protective earth (PE) conductor cross-section is to be dimensioned as per (PE) EN61800-5-1.
For typical mains cable fuses, refer to chapter “Fuses”.
PE-conductor
According to EN61800-5-1, the cross-sections of the PE conductor shall be dimensioned as follows:
Mains cable
Protective conductor
Mains cable up to 10 mm²
Install two protective conductors of the same size as the mains cable, or
one protective conductor of a size of 10 mm².
Mains cable 10…16 mm²
Install one protective conductor of the same size as the mains cable.
Mains cable 16…35 mm²
Install one protective conductor of a size of 16 mm².
Mains cable > 35 mm²
Install one protective conductor of half the size of the mains cable.
The following table provides an overview of typical conductor cross-sections (copper cable with PVC
insulation, 30 °C ambient temperature, continuous mains current max. 100% nominal input current). Actual
mains cable cross-section requirements may deviate from these values depending on actual operating
conditions.
Mains connection
AEC 401
Mains cable
PE-conductor
-19
9.7 kVA
2.5 mm²
2x2.5 mm² or 1x10 mm²
-21
12.5 kVA
2.5 mm²
2x2.5 mm² or 1x10 mm²
-22
15.2 kVA
4 mm²
2x4 mm² or 1x10 mm²
-23
17.3 kVA
4 mm²
2x4 mm² or 1x10 mm²
-25
22.2 kVA
6 mm²
2x6 mm² or 1x10 mm²
-27
27.7 kVA
10 mm²
1x10 mm²
-29
31.2 kVA
10 mm²
1x10 mm²
-31
41.6 kVA
16 mm²
1x16 mm²
-33
52.0 kVA
25 mm²
1x16 mm²
-35
62.3 kVA
35 mm²
1x16 mm²
-37
76.2 kVA
35 mm²
1x16 mm²
-39
86.6 kVA
50 mm²
1x25 mm²
Содержание AEC 401 Series
Страница 1: ...Device Series Active Energy Control AEC 401 Operating Instructions ...
Страница 2: ......
Страница 88: ......
Страница 89: ......