Operating Instructions AEC
11/17
6.3
Technical Data – Control Electronic Equipment
Control terminal X210A
Control terminal X210B
X210A.1
DC 20 V output (I
max
=180 mA) or DC
24 V ±10% input for external power
supply
X210B.1
Digital inputs
2)
X210A.2
GND 20 V/ GND 24 V (ext.)
X210B.2
3)
Digital input S7IND
X210A.3
Digital input S1IND for release and
acknowledging errors
1)
X210B.3
Digital output
2)
X210A.4
Digital inputs
2)
X210B.4
Multifunction output
2)
X210A.5
X210B.5
DC 10 V output (I
max
=4 mA)
X210A.6
X210B.6
multifunction input
2)
X210A.7
X210B.7
Ground 10 V
Relay output X10
X10
Wire with precharging circuit or with network
access.
See chapter “8.3.3.3”/“8.3.4.3”.
1)
Release of mains unit: Contact at X210A.3 must be closed.
2)
Control terminals are freely configurable.
3)
Release of mains unit: Contact at X210B.2 must be closed.
Control terminals are assigned certain default settings. These settings can be adjusted to
the specific application. You can assign various functions to the control terminals.
Technical data of control terminals
Digital inputs (X210A.3…X210B.2): PLC compatible
Low Signal: DC 0 V … 3 V, High signal: DC 12 V … 30 V,
Input resistance: 2.3 kΩ, response time: 2 ms , except for X210A.3 and X210B.2 response time:
10 ms
Digital output (X210B.3):
Low Signal: DC 0 V … 3 V, High signal: DC 12 V … 30 V,
Maximum output current: 50 mA, PLC compatible
Multifunction output (X210B.4):
Analog signal: DC 19 … 28 V, maximum output current: 50 mA, pulse-width modulated (f
PWM
= 116 Hz),
Digital signal: Low Signal: DC 0 V … 3 V, High signal: DC 12 V … 30 V, output current: 50 mA, PLC compatible
Frequency signal: Output voltage: DC 0 V … 24 V, maximum output current: 40 mA,
maximum output frequency: 150 kHz
Multifunction input (X210B.6):
Analog signal: Input voltage: DC 0… 10 V (Ri=70 kΩ), input current: DC 0 mA … 20 mA (R
i
=500 Ω),
Digital signal: Low Signal: DC 0 V … 3 V, High signal: DC 12 V…30 V, response time: 4 ms, PLC compatible
Relay output (X10):
Change-over contact, response time approx. 40 ms
Make contact AC 5 A / 240 V, DC 5 A (ohmic) / 24 V,
Break contact AC 3 A / 240 V, DC 1 A (ohmic) / 24 V
For connection of a coupler relay for controlling power contactors. Note the technical data of the existing
customer-provided components.
Conductor cross-section:
The signal terminals are suitable for the following cable sizes:
with ferrule: 0.25 mm² … 1.0 mm²
without ferrule: 0.14 mm² … 1.5 mm²