11/17
Operating Instructions AEC
85
Parameter
Setting
No.
Description
Min.
Max.
Factory
setting
700
Amplification
0.00
80.00
0.6
701
Integral Time
0.00 ms
10.00 ms
10.00 ms
800
Operation Mode
Voltage Controller
1 –
Voltage Control
1
801
Reference DC-Link Voltage
390.0 V
675.0 V
775.0 V
802
Max. DC-Link Voltage
Deviation
10.0 V
75.0 V
200.0 V
803
Max. Output Current
1.6 A
I
nominal
2 * I
nominal
804
Max. Feed Current
0.0 A
2 * I
nominal
2 * I
nominal
805
Max. Feedback Current
0.0 A
2 * I
nominal
2 * I
nominal
810
Operation Mode Filter
Compensation
1 –
2 –
11 –
12 –
without overload
with overload
without overload,
with react. current priority
without overload,
without react. current priority
11
For the setting options of other parameters, see ACU frequency inverters operating
instructions.