18 

 

2.2.5

 

Programming the Module 

To  be  adjusted  to  a  specific  use  case,  the  module  supports  changing  configuration  parameters 

stored in its non-volatile memory by means of the UProg software utility (version 4.1.0.48 or higher). A 
personal computer and one of the interface converters PI-GR, S2000-PI, S2000-USB, USB-RS485, or 
S2000

М

 (version 2.03 or higher) are to be in use. The last version of UProg Configuration Tool along 

with  additional  information  relating  to  operating  the  module  can  be  found  online  at 

http://bolid.ru

Table 2.2.5.1 describes configuration parameters of the module. 

Table 2.2.5.1.

 Module’s Configuration Parameters

 

Parameter 

Description 

Range 

Default Value 

1. Network Address 

The address of the module in the 
line of the RS-485 interface bus 

1 – 127 

127 

2. Response Pause 

The admissible delay for the 
module to answer requests of 
the network controller 

(1.5 – 500) ms 

1.5 ms 

3. Partition Number 

The  number  of  the  Orion  system 
partition associated with the LED 

0 – 9999 

1-60 

4. Indicator Type 

Defines  performance  of  the 
indicator  depending  on  the  type 
of  alarm  loops  combined  to  the 
partition 

Intrusion 
Fire 
Auxiliary 
Intrusion 2 
Auxiliary 2 
Engineering 
Auxiliary 3 
Actuator 
Intrusion 3 
Fault 
Leakage Monitoring 
Door Monitoring 
Access Control 

Intrusion 

5. Button Action 

Defines  the  effect  of  pressing  on 
the button 

Unused 

Arm 
Disarm 
Arm / Disarm 
Turn the actuator off 
Turn the actuator on 
Turn the actuator on/off 
Reset 

Arm / Disarm 

6. Audio Alarm Duration 
for Fire2, Fire, Fire 
Prealarm Conditions 

Sound  alarms  can  be  disabled 
provided  that  the  S2000M 
panel  is  located  closely  to  the 
module 

Off: Disabled,   
otherwise 

the 

buzzer 

sounds infinitely 

Infinitely 

7. Audio Alarm Duration 
for Fault 

The  time  on  elapsing  which  a 
sound 

alarm 

is 

silenced 

automatically. 
Sound  alarms  can  be  disabled 
provided  that  the  S2000M 
panel  is  located  closely  to  the 
module 

(0 – 255) s 
255 means unlimited time 

255 

8. Audio Alarm Duration 
for Discharge /Activation 

255 

9. Audio Alarm Duration 
for Attack (Panic Alarm, 
Duress) 

The time on elapsing which a 
sound alarm is silenced 
automatically. 

255 

10. Audio Alarm 
Duration for Intrusion 

255 

Содержание S2000-BKI

Страница 1: ...CONTROL BUTTON AND INDICATOR MODULE S2000 BKI User s Manual ...

Страница 2: ...esign 16 2 2 3 Mounting 16 2 2 4 Connecting the Module 17 2 2 5 Programming the Module 18 2 2 6 Updating Firmware 19 2 2 7 Testing Operability 19 2 2 8 Extreme Situation Actions 19 3 Maintenance 19 3 1 General 19 3 2 Safety Precautions 19 3 3 Maintenance Procedures 19 3 4 Performance Testing 20 3 4 1 Inspecting Operability 20 3 4 2 Checking in the Indication Test mode 20 3 5 Technical Examination ...

Страница 3: ...icator Module of version 2 45 Only the personnel who have studied this manual are allowed to operation activities All activities on mounting programming and commissioning shall be performed in compliance with the requirements of the regulatory documentation in force at the place of operation ...

Страница 4: ...s a component of the control and indicating intrusion alarm equipment it is allowed to be connected to an external reader module 1 1 4 By the capability of expanding functionality or quantitative aspects the module is classed as a non expandable product 1 1 5 The module provides a capability of using means of computer facilities for monitoring and programming 1 1 6 The module is classed as a repar...

Страница 5: ...s delivery scope Table 1 3 1 Item Q ty pcs S2000 BKI Control Button and Indicator Module 1 Accessory Kit Woodscrew 1 3х25 016 GOST 1144 80 3 Wall plug 6х30 3 Packaging 1 Documentation S2000 BKI Operations Manual 1 1 4 Arrangement and Operation 1 4 1 The module appears as shown in Figure 1 see 2 2 2 1 4 2 Light indication is provided by means of 60 bicolor LEDs to display states of up to 60 fire al...

Страница 6: ...ry Low Backup Battery Low Level Above Limit Level Below Limit Noise Actuator Failed Actuator Error Service Required Temperature Sensor Fault Input Communication Fault Output Communication Fault Unit Communication Fault Device Authentication Error PL Short Circuit PL Overvoltage PL Communication Error PL Unstable Error PL1 Communication Lost PL2 Communication Lost Communication Link Failure Activat...

Страница 7: ...re on the S2000M panel Table 1 4 5 Performance of the 1 60 LEDs for Indicators of Fire Type Partition Condition Performance of the 1 60 Indicators Fire2 Alarm Lit steady with red Fire Alarm Blinks in red with 0 25 s on and 0 25 s off Fire Prealarm Blinks in red with 0 25 s on and 1 75 s off Fault Blinks in amber with 0 25 s on and 1 75 s off Arming Failed Blinks in amber with 0 5 s on and 0 5 s of...

Страница 8: ...iliary and Auxiliary 2 imply that the relevant partition contains only auxiliary alarm loop and potential troubles of this loop are indicated with the highest priority These two tactics differ from each other by the way of indicating activation of the auxiliary alarm loop for Auxiliary type the LED illuminates steady with red while for Auxiliary 2 type the LED pulses with amber For the type Auxili...

Страница 9: ... of the 1 60 LEDs for Indicators of Leakage Monitoring Type Partition Condition 1 60 LEDs Performance Flooding Alarm Blinks in red with 0 5 s on and 0 5 s off Fault Blinks in amber with 0 25 s on and 1 75 s off Flood Detector Restored Lit steady with green Disarmed Off Disabled Lit steady with amber Note S2000M Fire and Alarm Control Panel of ver 3 00 or higher shall be in use Table 1 4 13 Perform...

Страница 10: ...ormance of Single Color LEDs Partition Condition LED Performance Fire 2 FIRE 2 Lit steady with red Fire FIRE Red 0 25 s on 0 25 s off Fire Prealarm PREALARM Red 0 25 s on 1 75 s off Intrusion Alarm Flooding Detected INTRUSION Red 0 5 s on 0 5 s off Panic Alarm Duress PANIC ALARM Red 0 5 s on 0 5 s off Arming Failed ARMING FAILED Amber 0 5 s on and 0 5 s off Disabled DISABLED Amber Fault FAULT Ambe...

Страница 11: ...essing on one of 1 to 60 buttons sends the network controller a request to execute one of the commands Arm Disarm Turn Actuator On Off Reset Alarms The network controller considers the received request and makes a decision about access to the requested action the relevant indicator blinking until the command is either executed or rejected Request to arm Request to disarm Request to switch the actu...

Страница 12: ...icators The buttons are operable within 20 s since the credential is presented the reader LED illuminates After pressing a permitted button it is kept to be operable again for 10 s To cancel permission for operation please push the Reset button The buttons 1 to 60 provide executing the following operations Table 1 4 20 How to Operate Partitions Using Control Buttons To disarm Press quickly on the ...

Страница 13: ...ended for transmission over local area networks fiber optic channels or radio channels Current values of Network Address and Response Pause can be unset to factory default values by successive pressing on the tamper switch three times for a long time and one time quickly dush dush dush dot A long press here means holding the tamper switch pressed for at least 1 5 s A quick press here is implied as...

Страница 14: ... meet the operation conditions defined in Section 1 2 of this manual 2 2 Preparing for Use 2 2 1 Safety Measures During Preparation The design of the module meets the requirements of electrical and fire safety in accordance with Russian Standards GOST 12 2 007 0 75 and GOST 12 1 004 91 The module has no circuits under a hazardous voltage Mounting and maintenance of the module should be carried out...

Страница 15: ... РД 78 145 92 Rules for Manufacturing and Commissioning Fire and Intrusion Alarm Installations The module shall be installed at a height that is suitable for operating and maintaining the equipment The module is to be installed on a wall or another structure at places protected against exposure to atmospheric precipitation and mechanical damage ...

Страница 16: ...djacently then vertical and horizontal distances between them shall be at least 10 mm each 2 2 4 Connecting the Module Connect wires to the terminals as shown in Figure 2 Figure 2 External Connection Diagram Please observe polarity while connecting the module to power supplies The cross section of wires should not exceed 1 5 sq mm If the module the control panel or other equipment connected to the...

Страница 17: ...ed with the LED 0 9999 1 60 4 Indicator Type Defines performance of the indicator depending on the type of alarm loops combined to the partition Intrusion Fire Auxiliary Intrusion 2 Auxiliary 2 Engineering Auxiliary 3 Actuator Intrusion 3 Fault Leakage Monitoring Door Monitoring Access Control Intrusion 5 Button Action Defines the effect of pressing on the button Unused Arm Disarm Arm Disarm Turn ...

Страница 18: ...ing takes several minutes The module can enter the updating mode as a result of an unexpected failure In this case updating restoring firmware under UProg exe helps return the module to normal operation without contacting a service center 2 2 7 Testing Operability Testing operability is conducted as described in Clause 3 4 of this manual 2 2 8 Extreme Situation Actions 3 Maintenance 3 1 General Th...

Страница 19: ...to the module and the panel The power LED of the module the upper LED near the device name shall show green solid light within 2 s Measure the current consumed by the module Its value shall not exceed 200 mA Within a minute since powering on the panel shall display a message about detecting a device with the network address currently assigned to the S2000 BKI factory value of the module address is...

Страница 20: ...nty repair Claims should be submitted to the following address NVP BOLID 4 Pionerskaya Str Korolyov Moscow Region 141070 Russia Phone fax 7 495 775 71 55 PBX E mail info bolid ru In case of any issue related to use of the product please contact the technical support 7 495 775 71 55 or e mail support bolid ru 5 Storage The module in the consumer package shall be stored as per Storage Conditions 1 i...

Страница 21: ...2000 BKI Control Button and Indicator Module meets the requirements of Technical Regulations of Eurasian Economic Union On Requirements for Fire Safety and Fire Extinguishing Equipment TR EAEU 043 2017 and is covered by the conformity certificate No ЕАЭС RU C RU ПБ68 В 00382 21 S2000 BKI Control Button and Indicator Module meets the requirements of Technical Regulations of Custom Union Electromagn...