background image

 

Intrusion-3

 Indicator Type is also intended to indicate conditions of intrusion alarm partitions. 

As opposite to 

Intrusion

 Indicator Type, troubles are indicated when there are no other conditions. 

Table 1.4.4.

 Performance of the 

“1” – “60”

 LEDs for Indicators of  

Intrusion-3

 Type

 

Partition Condition 

Performance of the “1” – “60” Indicators 

Panic Alarm, Flooding Detected, 

Intrusion Alarm 

Blinks in red with 0.5 s on and 0.5 s off 

Arming Failed 

Blinks in amber with 0.5 s on and 0.5 s off 

Lobby Alarm 

Blinks in red with 0.25 s on and 0.75 s off 

Disarmed 

Lit steady in green 

Arming 

Blinks in green four times per second 

Armed 

Lit steady in red 

Fault 

Blinks in amber with 0.25 s on and 1.75 s off 

Disabled 

Lit steady in amber (under S2000M ver.3.00+) 

Note: 

Intrusion-3

 Indicator Type operates correctly only with S2000M Fire and Alarm Control Panel 

of ver.2.03 or higher. 

Fire

 Indicator Type is also intended to indicate conditions of individual fire partitions (zones). 

General indicators Fire, Fault, and Disabled of modular fire protection equipment are on the S2000M 
panel. 

Table 1.4.5.

 Performance of the 

“1” – “60”

 LEDs for Indicators of 

Fire

 Type

 

Partition Condition 

Performance of the “1” – “60” Indicators 

Fire2 Alarm 

Lit steady with red 

Fire Alarm 

Blinks in red with 0.25 s on and 0.25 s off 

Fire Prealarm 

Blinks in red with 0.25 s on and 1.75 s off 

Fault 

Blinks in amber with 0.25 s on and 1.75 s off 

Arming Failed 

Blinks in amber with 0.5 s on and 0.5 s off 

Arming 

Blinks in green four times per second 

Armed, Restored, Noise Removed, Mains 

Restored, Battery Restored, Output Normal, 

Tamper Restored, PL Normal, 

Charger Normal, Link Restored, 

Output Communication Normal, 

Input Communication Normal, PL1 Com 

Restored, PL2 Com Restored, DC ON, 

Load Normal, Power Restored, Battery 2  

Normal, Unit Communication Normal 

Lit steady with green 

Disabled 

Lit steady with amber 

Note: S2000M Fire and Alarm Control Panel of ver.3.00 or higher shall be in use. 

Fault

 Indicator Type is intended for indicating faults only and is applicable as to intrusion and 

fire detection partitions (zones). 

Table 1.4.6.

 Performance of the 

“1” – “60”

 LEDs for Indicators of 

Fault

 Type 

Partition Condition 

«1” – “60” LEDs Performance 

Fault 

Blinks in amber with 0.25 s on and 1.75 s off 

Disarmed 

Lit steady with amber 

Disabled 

Lit steady with amber 

Содержание S2000-BKI

Страница 1: ...CONTROL BUTTON AND INDICATOR MODULE S2000 BKI User s Manual ...

Страница 2: ...esign 16 2 2 3 Mounting 16 2 2 4 Connecting the Module 17 2 2 5 Programming the Module 18 2 2 6 Updating Firmware 19 2 2 7 Testing Operability 19 2 2 8 Extreme Situation Actions 19 3 Maintenance 19 3 1 General 19 3 2 Safety Precautions 19 3 3 Maintenance Procedures 19 3 4 Performance Testing 20 3 4 1 Inspecting Operability 20 3 4 2 Checking in the Indication Test mode 20 3 5 Technical Examination ...

Страница 3: ...icator Module of version 2 45 Only the personnel who have studied this manual are allowed to operation activities All activities on mounting programming and commissioning shall be performed in compliance with the requirements of the regulatory documentation in force at the place of operation ...

Страница 4: ...s a component of the control and indicating intrusion alarm equipment it is allowed to be connected to an external reader module 1 1 4 By the capability of expanding functionality or quantitative aspects the module is classed as a non expandable product 1 1 5 The module provides a capability of using means of computer facilities for monitoring and programming 1 1 6 The module is classed as a repar...

Страница 5: ...s delivery scope Table 1 3 1 Item Q ty pcs S2000 BKI Control Button and Indicator Module 1 Accessory Kit Woodscrew 1 3х25 016 GOST 1144 80 3 Wall plug 6х30 3 Packaging 1 Documentation S2000 BKI Operations Manual 1 1 4 Arrangement and Operation 1 4 1 The module appears as shown in Figure 1 see 2 2 2 1 4 2 Light indication is provided by means of 60 bicolor LEDs to display states of up to 60 fire al...

Страница 6: ...ry Low Backup Battery Low Level Above Limit Level Below Limit Noise Actuator Failed Actuator Error Service Required Temperature Sensor Fault Input Communication Fault Output Communication Fault Unit Communication Fault Device Authentication Error PL Short Circuit PL Overvoltage PL Communication Error PL Unstable Error PL1 Communication Lost PL2 Communication Lost Communication Link Failure Activat...

Страница 7: ...re on the S2000M panel Table 1 4 5 Performance of the 1 60 LEDs for Indicators of Fire Type Partition Condition Performance of the 1 60 Indicators Fire2 Alarm Lit steady with red Fire Alarm Blinks in red with 0 25 s on and 0 25 s off Fire Prealarm Blinks in red with 0 25 s on and 1 75 s off Fault Blinks in amber with 0 25 s on and 1 75 s off Arming Failed Blinks in amber with 0 5 s on and 0 5 s of...

Страница 8: ...iliary and Auxiliary 2 imply that the relevant partition contains only auxiliary alarm loop and potential troubles of this loop are indicated with the highest priority These two tactics differ from each other by the way of indicating activation of the auxiliary alarm loop for Auxiliary type the LED illuminates steady with red while for Auxiliary 2 type the LED pulses with amber For the type Auxili...

Страница 9: ... of the 1 60 LEDs for Indicators of Leakage Monitoring Type Partition Condition 1 60 LEDs Performance Flooding Alarm Blinks in red with 0 5 s on and 0 5 s off Fault Blinks in amber with 0 25 s on and 1 75 s off Flood Detector Restored Lit steady with green Disarmed Off Disabled Lit steady with amber Note S2000M Fire and Alarm Control Panel of ver 3 00 or higher shall be in use Table 1 4 13 Perform...

Страница 10: ...ormance of Single Color LEDs Partition Condition LED Performance Fire 2 FIRE 2 Lit steady with red Fire FIRE Red 0 25 s on 0 25 s off Fire Prealarm PREALARM Red 0 25 s on 1 75 s off Intrusion Alarm Flooding Detected INTRUSION Red 0 5 s on 0 5 s off Panic Alarm Duress PANIC ALARM Red 0 5 s on 0 5 s off Arming Failed ARMING FAILED Amber 0 5 s on and 0 5 s off Disabled DISABLED Amber Fault FAULT Ambe...

Страница 11: ...essing on one of 1 to 60 buttons sends the network controller a request to execute one of the commands Arm Disarm Turn Actuator On Off Reset Alarms The network controller considers the received request and makes a decision about access to the requested action the relevant indicator blinking until the command is either executed or rejected Request to arm Request to disarm Request to switch the actu...

Страница 12: ...icators The buttons are operable within 20 s since the credential is presented the reader LED illuminates After pressing a permitted button it is kept to be operable again for 10 s To cancel permission for operation please push the Reset button The buttons 1 to 60 provide executing the following operations Table 1 4 20 How to Operate Partitions Using Control Buttons To disarm Press quickly on the ...

Страница 13: ...ended for transmission over local area networks fiber optic channels or radio channels Current values of Network Address and Response Pause can be unset to factory default values by successive pressing on the tamper switch three times for a long time and one time quickly dush dush dush dot A long press here means holding the tamper switch pressed for at least 1 5 s A quick press here is implied as...

Страница 14: ... meet the operation conditions defined in Section 1 2 of this manual 2 2 Preparing for Use 2 2 1 Safety Measures During Preparation The design of the module meets the requirements of electrical and fire safety in accordance with Russian Standards GOST 12 2 007 0 75 and GOST 12 1 004 91 The module has no circuits under a hazardous voltage Mounting and maintenance of the module should be carried out...

Страница 15: ... РД 78 145 92 Rules for Manufacturing and Commissioning Fire and Intrusion Alarm Installations The module shall be installed at a height that is suitable for operating and maintaining the equipment The module is to be installed on a wall or another structure at places protected against exposure to atmospheric precipitation and mechanical damage ...

Страница 16: ...djacently then vertical and horizontal distances between them shall be at least 10 mm each 2 2 4 Connecting the Module Connect wires to the terminals as shown in Figure 2 Figure 2 External Connection Diagram Please observe polarity while connecting the module to power supplies The cross section of wires should not exceed 1 5 sq mm If the module the control panel or other equipment connected to the...

Страница 17: ...ed with the LED 0 9999 1 60 4 Indicator Type Defines performance of the indicator depending on the type of alarm loops combined to the partition Intrusion Fire Auxiliary Intrusion 2 Auxiliary 2 Engineering Auxiliary 3 Actuator Intrusion 3 Fault Leakage Monitoring Door Monitoring Access Control Intrusion 5 Button Action Defines the effect of pressing on the button Unused Arm Disarm Arm Disarm Turn ...

Страница 18: ...ing takes several minutes The module can enter the updating mode as a result of an unexpected failure In this case updating restoring firmware under UProg exe helps return the module to normal operation without contacting a service center 2 2 7 Testing Operability Testing operability is conducted as described in Clause 3 4 of this manual 2 2 8 Extreme Situation Actions 3 Maintenance 3 1 General Th...

Страница 19: ...to the module and the panel The power LED of the module the upper LED near the device name shall show green solid light within 2 s Measure the current consumed by the module Its value shall not exceed 200 mA Within a minute since powering on the panel shall display a message about detecting a device with the network address currently assigned to the S2000 BKI factory value of the module address is...

Страница 20: ...nty repair Claims should be submitted to the following address NVP BOLID 4 Pionerskaya Str Korolyov Moscow Region 141070 Russia Phone fax 7 495 775 71 55 PBX E mail info bolid ru In case of any issue related to use of the product please contact the technical support 7 495 775 71 55 or e mail support bolid ru 5 Storage The module in the consumer package shall be stored as per Storage Conditions 1 i...

Страница 21: ...2000 BKI Control Button and Indicator Module meets the requirements of Technical Regulations of Eurasian Economic Union On Requirements for Fire Safety and Fire Extinguishing Equipment TR EAEU 043 2017 and is covered by the conformity certificate No ЕАЭС RU C RU ПБ68 В 00382 21 S2000 BKI Control Button and Indicator Module meets the requirements of Technical Regulations of Custom Union Electromagn...

Отзывы: