5
1
Description and Operation
1.1
Purpose
1.1.1
S2000-BKI Control Button and Indicator Module (hereinafter referred to as the module) is
designed to operate under a network controller (S2000M Monitoring and Control Panel for Fire and
Intrusion Alarm Systems, Sirius Fire Alarm Control Panel, or their modifications) as a modular
component of a:
−
Control and indicating equipment for fire / intruder alarm systems;
−
Fire protection equipment controls.
The network controller is allowed to be a personal computer with installed Orion Pro Software
Suite. In this case the module is intended to be used as a component of control and indicating intrusion
alarm equipment.
1.1.2
The module is designed to provide:
−
Light and sound indication of conditions of fire and intrusion alarm and auxiliary partitions as
well as conditions of actuators and control appliances of fire protection equipment;
−
Operating (arming / disarming) fire and intrusion alarm partitions remotely;
−
Operating actuators and control appliances of fire protection equipment remotely.
1.1.3
Access to system controls is performed using the built-in iButton reader. When the module
operates as a component of the control and indicating intrusion alarm equipment, it is allowed to be
connected to an external reader module.
1.1.4
By the capability of expanding functionality or quantitative aspects, the module is classed as a
non-expandable product.
1.1.5
The module provides a capability of using means of computer facilities for monitoring and
programming.
1.1.6
The module is classed as a reparable, recoverable, monitorable, regularly maintainable, and
multifunctional product.
1.1.7
The module is intended for round-the-clock operation.
1.1.8
The module’s design doesn’t imply operating it in aggressive and dusty environments or in ex-
hazardous premises.
1.2
Specifications
Specifications are given in Table 1.2.1.
Table 1.2.1
No.
Parameter
Value
1.2.1
DC power voltage, V
10.2 … 28.4
1.2.2
Max current consumption, mA:
- in the quiescent mode (all the LEDs are off at 12V/24V input power)
- in the alarm mode (12V input power)
- in the alarm mode (24V input power)
50
200
100
1.2.3
Power inputs
2
1.2.4
Max Start-up Time, s
5
1.2.5
Number of Partitions (Discharge Zones)
60
1.2.6
Enclosure protection degree as per GOST 14254-2015
I
Р
20
1.2.7
Environmental category as per OST 25 1099-83
О
3
1.2.8
Operating temperature, °C
-30 … +50
1.2.9
Max relative humidity, % (at +40 °C)
93
1.2.10
Resistance to mechanical exposure as per OST 25 1099-83
Arrangement
Category III