13
Conditions
Sounding Pattern
Intrusion Alarm
0.25 s On / 0.25 s Off
Panic Alarm
0.25 s On / 0.25 s Off
Fault
0.25 s On / 1.75 s Off
Access Request (touching with an iButton)
Turns on for 0.25 s
Access Denied (for the iButton)
Turns on for 1 s
Access Granted
Turns on for 0.25 s
Offline
0.25 s On / 1.75 s Off
Others
Off
1.4.8
The buzzer can be silenced by pressing
.
The UProg utility provides restricting access to silencing sound signals. In such case the button
is
disabled, and the activated buzzer is turned off after touching the iButton reader with one of iButtons
which codes are enrolled in the module’s memory. Sounds can be silenced automatically except for Fire
Prealarm, Fire Alarm, Fire 2 Alarm if the relevant options are defined in the module’s configuration.
Duration of sounds is selected while configuring the module. In this case no message about silencing is
sent to the network controller.
1.4.9
Partitions can be operated (armed / disarmed) using control buttons in two ways: with restricting
access to operations (via an iButton) or with free access to operations.
1.4.10
In case of
restricted access
, the module’s buttons are effective only after authorization
performed by user’s presenting the relevant credential to the in-built iButton reader or to a reader
connected to the module. The credential shall be previously programmed to operate partitions: a list of
partitions permitted for operation and permitted actions shall be defined. The partitions in question
shall also be related to the relevant module indicators.
The buttons are operable within 20 s since the credential is presented (the reader LED illuminates).
After pressing a permitted button it is kept to be operable again for 10 s. To cancel permission for
operation, please push the Reset button
.
The buttons “1” to “60” provide executing the following operations:
Table 1.4.20
. How to Operate Partitions Using Control Buttons
To disarm
Press quickly on the button when the partition has one of the states
Armed, Arming Failed, Intrusion, Fire Prealarm, Fire Alarm
To arm
Press quickly on the button when the partition is in the Disarmed state
To turn the actuator on
Press quickly on the button when the partition is in the Actuator in Initial
Position state
To turn the actuator off
Press quickly on the button when the partition is in the Actuator in
Operating Position state or Actuator Failed state
To reset alarms
Press quickly on the button
1.4.11
In case of
free access
to operating partitions, an access code shall be assigned to the module and
written into its configuration by means of the UProg utility. The module sends the network controller
this code upon pushing any of the buttons “1” to “60”. The same code along with the relevant
authorities to operate partitions shall be enrolled into the network controller database.
1.4.12
The module sends the network controller the following messages over the RS-485 interface:
Tamper Alarm
The module’s enclosure has been open (the cover panel has been removed)
Tamper Restored
The module’s enclosure has been closed (the cover panel has been put into place)
Power Failed
The power voltage has dropped below a permissible threshold
Power Restored
The power voltage has been in the normal range
Test
Indication test has been run