20
− Relative humidity 45% through 80%;
− Ambient temperature 15
°
C through 35
°
C;
− Atmospheric pressure 630 mm Hg through 800 mm Hg (84 through 106.7 kPa).
3.3.4
While inspecting the module, always shut off the module’s power before connecting and
disconnecting its external circuits.
3.3.5
Testing procedures include inspecting operability and testing indication in the Indication Test
mode.
3.3.6
Preparations for testing the module includes:
a)
Check the package conditions and unpack the module;
b)
Check the delivery to comply with Section 1.3 of this manual, presence and content of
the accessory kit, serial number of the module and its production date to comply with those
ones specified in the operation manual;
c)
Ensure the module enclosure is not damaged;
d)
Shake the module and ensure there are no foreign bodies within it;
e)
Ensure that the terminal blocks are fastened properly.
3.3.7
To test operability of the module, please follow the instructions of Section 3.4 of this
manual.
3.4
Performance Testing
3.4.1
Inspecting Operability
To inspect the module, use an S2000M panel. Connect the module’s RS-485 circuits and power
circuits to the relevant terminals of the panel.
Connect a milliammeter in series with the power circuit of the module.
Apply power to the module and the panel.
The power LED of the module (the upper LED near the device name) shall
show green solid light within 2 s.
Measure the current consumed by the module. Its value shall not exceed
200 mA.
Within a minute since powering on, the panel shall display a message about
detecting a device with the network address currently assigned to the S2000-BKI
(factory value of the module address is 127). Figure 3 shows the display of the
S2000M panel with the relevant message.
If several messages accumulated by the module have been received by the panel, you can browse
them by the arrow buttons «
◄
» and «
►
» on the S2000M.
3.4.2
Checking in the Indication Test mode
Initiate the self-diagnostic mode for the module by selecting the Indication Test command in the
S2000M menu followed by selecting the module address (the factory address of the module is 127); see
the S2000M user’s manual for details.
If the module is operable, its indicators turn on in the following order:
a)
The columns of LEDs “1” – “60” turn on with amber one-by-one; the indicator FIRE 2 turns on
with amber; the reader LED turns on with amber; the indicators ARMING FAILED, DISABLED, FAULT
turn on with amber;
b)
The rows of LEDs “1” – “60” turn on with amber one-by-one, FIRE 2, FIRE, INTRUSION,
PANIC ALARM, the reader LEDs turn on with red, then , FIRE 2 (with changing color), FIRE,
PREALARM, INTRUSION, PANIC ALARM, ARMING FAILED, FAULT, DISABLED, and the reader
LED (with changing color) turn on one-by-one;
Figure 3