CT-600-2
89
13.4
Overview of parameters in CM-IO – oil and economizer system
Only parameters different from default are shown here. Further information see ST-150.
Parameter
Section
User Setting
COM 1 address
COM 1
Oil system: 11
Eco system: 12
Compressor type selection
Config
None
Discharge pressure selection
Config
PE 5000-5093-2: 0.00-32.00 bar(g)
PE 5000-5094-3: 0.00-34.47 bar(g)
(acc. to actual type used)
Suction pressure selection
Config
PE 5000-5093-2: 0.00-32.00 bar(g)
PE 5000-5094-3: 0.00-34.47 bar(g)
(acc. to actual type used)
Dedicated OEM functionality selection
Config
Remote IO
Mains supply voltage specification (single
phase)
Config
230 / 115 (depending on region)
Compressor serial number (actual)
CompInfo
Number as on name plate for oil
separator or economizer
Customer, Location
CompInfo
Site description
System name, Compressor number
CompInfo
ACP type designation and oil
separator or economizer type
Serial Control Source
SerCtrlCfg
COM1 (MODBUS)
Serial Communication Timeout Function
SerCtrlCfg
Fault
Serial Communication Timeout
SerCtrlCfg
15
13.5
Overview of parameters in M172 – electrical panel I/O
List of parameters set in Settings page for electrical panel IO-module (M172). Actual setup may be different,
according to sensor types used.
Communication parameters
Communication port
Setting
Default value
Ethernet
IP
10.4.156.21
Subnet
255.255.255.0
Gateway
10.4.156.1
RS485-1 & RS 485-2
Node/Modbus address
10
Data bit
8
Stop bit
1
Parity
Even
Baudrate
19200