2.18 Oil separator
level high
Surveillance for high level in oil
separator. A warning is issued when the
high level sensor detects oil (only when
at least one compressor is running).
19
2.19 Oil separator
coalescer level
high
Surveillance for high level in the
coalescer part of the oil separator. A
warning is issued when the coalescer
level sensor detects oil for the timer
period (only when at least one
compressor is running).
20
9
2.20 Oil separator
load high
Surveillance for high load (gas flow) in
the oil separator. A warning is issued
when the warning limit is exceeded. An
alarm is issued when the alarm limit is
exceeded or the warning limit is
exceeded for the timer period.
21
77, 78
10
2.21 Motor current
high
Surveillance for high motor current. A
warning is issued when the warning
limit is exceeded. An alarm is issued
when the alarm limit is exceeded or the
warning limit is exceeded for the timer
period.
151, 152,
153
65, 66
34
2.22 Total current
high
Surveillance for high total current
consumption. A warning is issued when
the warning limit is exceeded. An alarm
is issued when the alarm limit is
exceeded or the warning limit is
exceeded for the timer period.
23
8, 9
11
2.23 Eco system
liquid level high
Surveillance for high refrigerant level in
the economizer. When at least one
compressor is running with eco-valve
enabled, then a warning is issued when
the high level sensor detects liquid
refrigerant and an alarm is issued,
when the warning is active for the timer
81
17