both options no eco related alarms may
be active.
3.18 Eco system
liquid valve
Eco liquid valve is only opened, when
the enabled economizer system has no
alarms and at least one compressor
eco-valve is open. When eco liquid
valve is opened, then the timer for the
economizer oil return delay is started.
21
3.19 Eco system
bypass valve
Bypass valve is closed when at least
one compressor eco-valve is open or
when the economizer system is not
active or not enabled.
3.20 Eco system oil
return valve
Economizer oil return solenoid valve is
opened when the economzier system is
enabled, has high oil level and at least
one compressor eco-valve is open. The
opening is delayed with a timer after
opening of liquid valve.
21
12.5
Alarm, warning and timer functions
No.
Function
Description
Related
alarms,
warnings
(see 14.1)
Related
param.
(see 13.1)
Related
timers
(see 13.2)
4.1
Warning handler Warning status is set and reset by
protection functions only. Warnings are
acknowledged automatically if the
status is reset.
"all"