- 34 -
CONDENSATE TRAP
14 CONDENSATE TRAP
14 .1 Function
The condensate trap "A" in Figure 14.1 and Figure 14.2 allows
the discharge of the condensate via the condensate drain pipe
avoiding in the mean time the escape of combustion products.
Figure 14 .1
A
If the drain pipe becomes blocked, or condensate cannot drain,
the condensate level in the trap rises until it affects the flame
detection probe, this will cause the boiler lock-out.
14 .2 Check the cleanness of the trap
The condensate drain pipe "A" (Figure 14.2) does not require any
particular maintenance but just check:
1 That no solid deposits have formed, if so remove them.
2 That the condensate drain piping is not clogged.
To clean the inside of the siphon, remove it and turn it upside
down to remove any dirt (see section "14.3 Removal" on page
34).
14 .3 Removal
Warning: isolate the boiler from the mains electrici-
ty supply before removing any covering or compo-
nent .
1 Remove the front and right case panels.
2 Disconnect the air manifold "B".
3 Using pliers, remove the spring "C" moving it to the left.
4 Remove the pipe "D" from the trap "A".
Figure 14 .2
A
B
C
D
5
Remove the trap "A", moving it upwards; from the grommet
"E".
6 Reassemble carrying out the removal operations in reverse
order.
Figure 14 .3
E
A