26
COMMANDS
ENGLISH
STANDARD Communication Protocol
101 … 132
Harmonic (H1 … H50) L-N voltage phase 1 (ENH)
134 … 165
Harmonic (H1 … H50) L-N voltage phase 2 (ENH)
167 … 198
Harmonic (H1 … H50) L-N voltage phase 3 (ENH)
19A … 1CB Harmonic (H1 … H50) phase 1 current (ENH)
1CD … 1FE Harmonic (H1 … H50) phase 2 current (ENH)
200 … 231
Harmonic (H1 … H50) phase 3 current (ENH)
0FF
None variable selected
030
Imported active energy
+Wh
031
Imported reactive inductive energy
+varhI
033
Imported reactive capacitive energy
+varhC
01C
Imported apparent energy (only for standard instrument version)
+VAh
090
Imported apparent inductive energy (ENH)
+VAhI
092
Imported apparent capacitive energy (ENH)
+VAhC
032
Exported active energy
-Wh
02E
Exported reactive inductive energy
-varhI
02F
Exported reactive capacitive energy
-varhC
01D
Exported apparent energy (only for standard instrument version)
-VAh
091
Exported apparent inductive energy (ENH)
-VAhI
093
Exported apparent capacitive energy (ENH)
-VAhC
Variables code (e.g. 030=Imported active energy) should be used only with the 2 last digits (e.g. 30) in case of the
following commands: WA0, WA1, WB0, WB1, WA4, WA5, WB4, WB5, WA8, WA9, WB8, WB9, WA2, WB2, WA6, WB6,
WA3, WB3, WA7, WB7.
4.5 Error
Messages
Nr
Description
E000
COMMAND ACKNOWLEDGE (NO ERROR)
Reception of a correct command.
E011 ERROR
COMMAND
Reception of an incorrect command.
E101
RECORDING DOWNLOAD ERROR1
Empty
fi
le.
E102
RECORDING DOWNLOAD ERROR2
End of fi le.
NOTE
A verifi cation error on BCC is not indicated; the reception of a complete message but with
incorrect BCC is completely ignored by the instrument.
Code Description
Symbol