15
COMMANDS
ENGLISH
STANDARD Communication Protocol
Data conversion:
1064
0001000001100100(BIN)00010(BIN)=year:00000=20
00; 00001=2001;00010=2002;.....11111=2031 000011
00100(BIN)=day:100(DEC)-31(january)-28(february)-
31(march)=10april
1801
time
(HHMM)
0542
maxV1=(data*FS*PT)/32768[FS=1000]=0542(HEX)=1346
(DEC)=(1346*1000)/32768=41.08V
0229
maxA1=(data*FS*PT)/32768[FS=12]=0229(HEX)=553(DEC)
=(553*12)/32768=0.205A
0016
maxP1=(data*FS*PT)/32768[FS=12000]=0016(HEX)=(DEC)
=(22*12)/32768=8.057kW
0016
maxS1=(data*FS*PT)/32768[FS=12000]=0016(HEX)=22(DEC)
=(22*12)/32768=8.057kVA
0000
maxQ1=(data*FS*PT)/32768[FS=12000]=0000(HEX)=00(DEC)
=(00*12)/32768=0kvar
04A0
maxPF1=(7FFF-data*FS)/32768[FS=1.000]=7B5F(HEX)=31583(DEC)
=(31583)/32768=0.9638inductive
3206
maxF=(data)/128=3206(HEX)=12806(DEC)=(12806)/
256=50.02Hz
06B2
maxTHD=(data)/128=06B2(HEX)=1714(DEC)=(1714)/128=13.39%
0369
maxHarm3=(data)/128=0369(HEX)=873(DEC)=(873)/128=6.82
%
> Vunbalance, Aunbalance are calculated like THD values
> Thermal currents are calculated with the following formula:
Ath=(data) * 2 * (CT
2
)
> The parameters with sign should be preconverted as follows:
if (data)>$7FFF, means that the value is negative, and should be converted
•
in complement of 2: data new = 0 - data
for PF parameters, if (data) > $7FFF => INDUCTIVE PF => the formula is:
•
(data-7FFF)/32768
for PF parameters, if (data) <= $7FFF => CAPACITIVE PF => the formula
•
is: (7FFF-data)/32768
R80.4 DAILY COUNTERS RECORDING DOWNLOAD - FIRST DATA BLOCK
R80.5 DAILY COUNTERS RECORDING DOWNLOAD - NEXT DATA BLOCK
R80.6
DAILY COUNTERS RECORDING DOWNLOAD - REPEAT LAST DATA BLOCK
Answer format (R80.4, R80.5, R80.6):
<STX>000100CC106100000164...<ETX><BCC>
0001
progressive number of the transmitted block
00CC
total number of characters transmitted in this block
1061
date
00000164...
data block: energy counters expressed in mWh, mvarh, mVAh (with
two words).
I n o rd e r, i n c a s e o f s t a n d a rd i n s t r u m e n t v e r s i o n :
•
+Wh,+varhI,+varhC,+VAh, -Wh,-varhI,-varhC,-VAh
In order, in case of ENH instrument version: +Wh,+varhI,+varhC,
•
+VAhI,+VAhC, -Wh,-varhI,-varhC,-VAhI,-VAhC
Data conversion:
En value = decimal data*CT*PT
R80.8
WAVEFORM CAPTURE RECORDING DOWNLOAD - HEADER (ENH)
Answer
format:
<STX>00010030053014150105138F3FC82000A000A000A000E000E000E0000001
1F7D000100040000<ETX><BCC>
Command Description
UBN310
UBN315
UBN3080