21
COMMANDS
ENGLISH
STANDARD Communication Protocol
W9F
CLEAR COUNTERS & SET DEFAULT
Format:
W9F=XXXXX
Available
values:
43000=clear energy counters
53000=clear digital input counters *
75430=clear all counters
75000=clear time of use counters (only 315/3080 ENH)
80000=clear trends (only 315/3080 ENH)
65000=set default instrument parameters
WD1.xxx
TIME OF USE - SCHEDULE SETUP (ENH)
xxx=
schedule number: 001
÷
120; 121=holiday schedule
It is possible to set:
Only schedule date: WD1.001=MMDD
•
Only a tariff change of the schedule: WD1.001=MMDDCCHHMMTT
•
More tariff changes of the schedule: WD1.001=MMDDCCHHMMTT...CCHHMMTT
•
It is not possible to set more than 8 tariff changes with a single command. Therefore,
to set all 15 tariff changes, it is necessary to send 2 commands.
Format:
WD1.xxx=MMDDCCHHMMTT...CCHHMMTT...CCHHMMTT...CCHHMMTT...
CCHHMMTT...CCHHMMTT...CCHHMMTT...CCHHMMTT<ETX><BCC>
MMDD
month, day: in decimal, ex. 23 november=1123
CC
tariff changes number; 01
÷
15
HHMM
hour, minutes: in decimal, ex. 17:38=1738
TT
tariff: 00
÷
05
Example:
WD1.001=0930010800050210000303120001041400020516000306180
0040720000508220005
WD9
TIME OF USE - HOLIDAYS SETUP (ENH)
Format:
WD9.0=A, X, MMDD...MMDD - fi rst 10 holidays
WD9.1=A, X, MMDD...MMDD - last 10 holidays
A
holidays ON/OFF: 0=OFF; 1=ON
X
Sat&Sun Enable; 0=disable; 1=enable
MMDD
holidays month and day
Example:
WD9.0=1,1,0101010604250602071408151101120812251226
WD7
DMD CALCULATION MODE
Format:
WD7=X
Available
values:
0=fi xed
1=slide
2=COM
3=DI1
4=DI2
5=DI3
6=DI4
Example:
WD7=1
WDF
DMD CALCULATION SYNCHRONIZATION THROUGH COM
WD8 CLOCK
FORMAT
Format:
WD8=X,Y
X
0=YYMMDD; 1=MMDDYY; 2=DDMMYY
Y
0=24h; 1=12h (AM/PM)
Example:
WD8=1,1
Command Description
UBN310
UBN315
UBN3080