22
COMMANDS
ENGLISH
STANDARD Communication Protocol
WDE LANGUAGE
Format:
WDE=XX
Available
values:
00=English
01=Deutsch
02=Français
03=Italiano
04=Español
Example:
WDE=00
W2F
EVENT LOG RECORDING MODE (ENH)
Format:
W2F=X
Available
values:
0=none
1=fi
ll
2=ring
Example:
W2F=2
W21
SET POINT 1 (ENH)
Format:
W21=XX,YYY.YY,ZZ,JJJ
XX
associated variable (see section 4.4)
YYY.YY
tripping value referring to the fullscale
ZZ
hysteresis percentage value referring to the tripping value
JJJ
delay time on threshold tripping (in seconds)
Example:
W21=00,050.00,15,010
W22
SET POINT 2 (ENH)
Format:
see W21
W23
SET POINT 3 (ENH)
Format:
see W21
W24
SET POINT 4 (ENH)
Format:
see W21
W25
SET POINT 5 (ENH)
Format:
see W21
W26
SET POINT 6 (ENH)
Format:
see W21
W27
SET POINT 7 (ENH)
Format:
see W21
W28
SET POINT 8 (ENH)
Format:
see W21
DIGITAL OUTPUT 1
WA0 PULSE
Format:
WA0=XX,YYY.Y,ZZZ
XX
associated variable (see section 4.4)
YYY.Y
pulse coeffi cient (ex. Wh/pulse)
ZZZ
pulse duration time (msec.)
Example:
WA0=30,150.0,250
Command Description
UBN310
UBN315
UBN3080