COMMANDS
ENGLISH
STANDARD Communication Protocol
R3D.01
MEASURED INSTANTANEOUS VARIABLES
In case of wiring mode: 3Ph-4W/3CT
Answer
format:
<STX>
V
Σ
V1 V2 V3 V12 V23 V31 A
Σ
A1 A2 A3 THDA1 THDA2 THDA3 AN PF
Σ
PF1
PF2 PF3 COSØ1* COSØ2* COSØ3* VA
Σ
VA1 VA2 VA3 W
Σ
W1 W2 W3 var
Σ
var1
var2 var3 +Wh +varhI +varhC +VAh -Wh -varhI -varhC -VAh F THDV1 THDV2 THDV3
WDMD VADMD ADMD RST <ETX><BCC>
Value
format:
Instantaneous values, parameters always positive
•
value on 4 digits with decimal point (5 characters) + multiplier (space, m, k, M, G, T, …)
Instantaneous values, parameters with sign (+ or -)
•
sign + value on 4 digits with decimal point (5 characters) + multiplier (space,
m, k, M, G, T, …)
Digital inputs
•
value on 8 digits with decimal point (9 characters) + multiplier (space, m, k, M, G, T, …)
Energy counters
•
sign + value on 8 digits with decimal point (9 characters) + multiplier (space,
m, k, M, G, T, …)
Phase reversal
•
value on 3 digits with decimal point (4 characters) + multiplier (space, m, k, M, G, T, …)
In case of wiring mode: 3Ph-3W/2CT
Answer
format:
<STX>V
Σ
NUL NUL NUL V12 V23 V31 A
Σ
A1 A2 A3 THDA1 NUL THDA3 NUL PF
Σ
NUL NUL NUL NUL NUL NUL VA
Σ
NUL NUL NUL W
Σ
NUL NUL NUL var
Σ
NUL NUL
NUL +Wh +varhI +varhC +VAh -Wh -varhI -varhC -VAh F NUL NUL NUL WDMD
VADMD ADMD RST<ETX> <BCC>
In case of wiring mode: 1Ph-3W/2CT
Answer
format:
<STX>
V
Σ
V1 V2 NUL V12 NUL NUL A
Σ
A1 A2 NUL THDA1 THDA2 NUL AN PF
Σ
PF1 PF2 NUL COSØ1* COSØ2* NUL VA
Σ
VA1 VA2 NUL W
Σ
W1 W2 NUL var
Σ
var1
var2 NUL +Wh +varhI +varhC +VAh -Wh -varhI -varhC -VAh F THDV1 THDV2 NUL
WDMD VADMD ADMD RST <ETX><BCC>
In case of wiring mode: 1Phase
Answer
format:
<STX> NUL V1 NUL NUL NUL NUL NUL NUL A1 NUL NUL THDA1 NUL NUL NUL
NUL PF1 NUL NUL COSØ1* NUL NUL NUL VA1 NUL NUL NUL W1 NUL NUL NUL
var1 NUL NUL +Wh +varhI +varhC +VAh -Wh -varhI -varhC -VAh F THDV1 NUL NUL
WDMD VADMD ADMD RST <ETX><BCC>
R3D
UPM 300A (NEW VERSION) COMPATIBLE ANSWER FORMAT
In case of wiring mode:3Ph-4W/3CT
Answer
format:
<STX>
V
Σ
V1 V2 V3 V12 V23 V31 A
Σ
A1 A2 A3 PF
Σ
PF1 PF2 PF3 VA
Σ
VA1 VA2
VA3 W
Σ
W1 W2 W3 var
Σ
var1 var2 var3 +Wh +varhI F WDMD ADMD RST NUL
<ETX><BCC>
Value
format:
see R3D
R3E
UPM 300 (OLD VERSION) COMPATIBLE ANSWER FORMAT
In case of wiring mode: 3Ph-4W/3CT
Answer
format:
<STX>
V
Σ
V1 V2 V3 V12 V23 V31 A
Σ
A1 A2 A3 PF
Σ
PF1 PF2 PF3 VA
Σ
VA1 VA2 VA3
W
Σ
W1 W2 W3 var
Σ
var1 var2 var3 +Wh +varhI F WDMD ADMD<ETX><BCC>
Value
format:
see R3D
Command Description
UBN310
UBN315
UBN3080