COMMANDS
ENGLISH
STANDARD Communication Protocol
1F=digital input1 event HIGH
20=digital input1 event LOW
21=digital input2 event HIGH
22=digital input2 event LOW
23=digital input3 event HIGH
24=digital input3 event LOW
25=digital input4 event HIGH
26=digital input4 event LOW
R9E
WAVEFORM CAPTURE SETTINGS (ENH)
Answer format (see W9E):
<STX>XXX,Y,Z,TT<ETX><BCC>
R74.0
TIME OF USE COUNTERS - PREVIOUS MONTH (tariffs 1,2,3 values)
R74.1
TIME OF USE COUNTERS - THIS MONTH (tariffs 1,2,3 values)
R74.2
TIME OF USE COUNTERS - PREVIOUS DAY (tariffs 1,2,3 values)
R74.3
TIME OF USE COUNTERS - TODAY (tariffs 1,2,3 values)
Answer format (R74.0, R74.1, R74.2, R74.3):
<STX><TOU1-consumption energy><TOU1-generated energy><TOU2-consumption
energy><TOU2-generated energy><TOU3-consumption energy><TOU3-generated
energy><ETX><BCC>
Where:
consumption
energy
<+Wh +VAhI +VAhC +varhI +varhC>
generated
energy
<-Wh -VAhI -VAhC -varhI -varhC>
R74.4
TIME OF USE COUNTERS - PREVIOUS MONTH (tariffs 4,5 values)
R74.5
TIME OF USE COUNTERS - THIS MONTH (tariffs 4,5 values)
R74.6
TIME OF USE COUNTERS - PREVIOUS DAY (tariffs 4,5 values)
R74.7
TIME OF USE COUNTERS - TODAY (tariffs 4,5 values)
Answer format (R74.4, R74.5, R74.6, R74.7):
<STX><TOU4-consumption energy><TOU4-generated energy><TOU5-consumption
energy><TOU5-generated energy><ETX><BCC>
Where:
consumption
energy
<+Wh +VAhI +VAhC +varhI +varhC>
generated
energy
<-Wh -VAhI -VAhC -varhI -varhC>
RD1.xxx
TIME OF USE (ENH) - SCHEDULE xxx
xxx
=schedule number; 001
÷
120; 121=holiday schedule
Answer
format:
If TOU is not set:
•
<STX>0000<ETX><BCC>
If only start shedule date is set:
•
<STX>MMDD<ETX><BCC>
If start schedule date and tariff changes are set:
•
<STX>MMDDCCHHMMTT...CCHHMMTT...CCHHMMTT<ETX><BCC>
MMDD
month, day: in decimal, ex. 23 november=1123
CC
tariff changes number; 01
÷
15
HHMM
hour, minutes: in decimal, ex. 17:38=1738
TT
tariff: 00
÷
05
RD9
TIME OF USE - HOLIDAYS (ENH)
Answer format (see WD9):
<STX>A,X,MMDD..MMDD<ETX><BCC>
Command Description
UBN310
UBN315
UBN3080