14
COMMANDS
ENGLISH
STANDARD Communication Protocol
double
word:
20
mA
21
VA
22
W
23
var
24
Wh
25
varh
26
VAh
<space>
separator between two fi elds
R80.0
MIN / AVG / MAX RECORDING SETUP & STATUS
Answer
format:
<STX>VV1,VV2,VV3,VV4,VV5,VV6,VV7,VV8,M,TT,W,YYMMDDHHMMSS(1),YYMMD-
DHHMMSS(2), DD<ETX><BCC>
VV1,VV2,…VV8
selected variable (see section 4.4)
M
recording mode:0=NONE; 1=FILL; 2=RING
TT
integration time to calculate the DMD: 01, 05, 10, 15, 30,
60 min or 61 in case of external (Synchronization with
DMD calculation)
W
start/stop: 0=NO; 1=YES
YYMMDDHHMMSS(1)
start recording date
YYMMDDHHMMSS(2)
stop recording date
DD
downloading data: 00=not available; 01=available
Example:
<STX>001,002,003,009,00A,00B,094,096,1,60,0,040229125559,040229125559,01
<ETX><BCC>
R80.7 RECORDINGS SIZE
Answer
format:
<STX>E E E E M M M M M M W W W W V V V V<ETX><BCC>
E E E E
energy recording size
M M M M M M
min/avg/max recording size
W W W W
waveform capture recording size (only 315/3080 ENH)
V V V V
event LOG recording size (ENH)
R80.1 MIN/AVG/MAX RECORDING DOWNLOAD - FIRST DATA BLOCK
R80.2 MIN/AVG/MAX RECORDING DOWNLOAD - NEXT DATA BLOCK
R80.3
MIN/AVG/MAX RECORDING DOWNLOAD - REPEAT LAST DATA BLOCK
Answer format (R80.1, R80.2, R80.3):
<STX>00010106106418010542053A0536022902270227001600160016001600160
01600000000000004A00458031F3206320031F8...<ETX><BCC>
0001
progressive number of block transmitted
0106
total number of characters transmitted in this block
10641801....31F8
data block: YYMMDminimum, average, maximum
of selected variables expressed with a word, as a fraction
of the fullscale.Conversion is carried out by the program on
the PC during transfer
Command Description
UBN310
UBN315
UBN3080