9
COMMANDS
ENGLISH
STANDARD Communication Protocol
Value
format:
Instantaneous values
•
sign (space, +, -) + value on 4 digits with decimal point (5 characters) + multiplier
(space, m, k, M, G, T, …)
Digital inputs and Energy counters
•
sign (space, +, -) + value on 8 digits with decimal point (9 characters) + multiplier
(space, m, k, M, G, T, …)
Phase reversal
•
sign (space, +, -) + value on 3 digits with decimal point (4 characters) + multiplier
(space, m, k, M, G, T, …)
In case of wiring mode: 3Ph-3W/2CT
Answer
format:
<STX>
V
Σ
NUL NUL NUL V12 V23 V31 A
Σ
A1 A2 A3 THDA1 NUL THDA3 NUL PF
Σ
NUL NUL NUL NUL NUL NUL NUL VA
Σ
NUL NUL NUL W
Σ
NUL NUL NUL var
Σ
NUL
NUL NUL IN1 IN2 IN3 IN4 +Wh +varhI +varhC +VAh -Wh -varhI -varhC -VAh F NUL
NUL NUL NUL RST <ETX><BCC>
In case of wiring mode: 1Phase
Answer
format:
<STX> NUL V1 NUL NUL NUL NUL NUL NUL A1 NUL NUL THDA1 NUL NUL NUL
NUL PF1 NUL NUL NUL COSØ1* NUL NUL NUL VA1 NUL NUL NUL W1 NUL NUL
NUL var1 NUL NUL IN1 IN2 IN3 IN4 +Wh +varhI +varhC +VAh -Wh -varhI -varhC
-VAh F THDV1 NUL NUL NUL RST <ETX><BCC>
R3D.02
MEASURED INSTANTANEOUS VARIABLES (ENH)
In case of wiring mode:3Ph-4W/3CT
Answer
format:
<STX> THDA1o THDA1e THDA2o THDA2e THDA3o THDA3e THDV1o THDV1e
THDV2o THDV2e THDV3o THDV3e <ETX><BCC>
R3D.03
MEASURED INSTANTANEOUS VARIABLES (ENH)
In case of wiring mode:3Ph-4W/3CT
Answer
format**:
<STX> AT1 AT2 AT3 Vub Aub +VAI +VAC -VAI -VAC <ETX><BCC>
**
: In case of 310 instrument, the apparent power values are not defi ned and ----- will
be displayed.
R3D.04
MEASURED INSTANTANEOUS VARIABLES (ENH)
In case of wiring mode:3Ph-4W/3CT
Answer
format:
<STX> K1 K2 K3 <ETX><BCC>
Command Description
UBN310
UBN315
UBN3080