Through the REC10 it is possible to access, using the TECHNICAL
menu, a series of parameters that can be programmed to allow you to
personalise the operation of the boiler based on the type of system.
- Then set the parameters according to the desired operating modes.
5.2.1
Boiler configuration
-
Access the technical parameters as explained in the section
-
Select PARAMETERS with the
“up”
and
“down”
keys, confirming the
selection.
-
TERMOREGOLAZIONE
PARAMETERS
INSTALLATION
THERMOREGULATION
RANGE RATED
TECHNICAL
INSTALLER
CALIBRATION
PARAMETERS
WEATHER COMPENSATION
INSTALLATION
RANGE RATED
CALIBRATION
TECHNICAL
INSTALLER
S
elect from among the following options with the
“up”
and
“down”
,
keys, confirming the selection.
-
PARAMETERS
INSTALLER
TIMER OFF CH
RESET TIMERS CH
PREHEATING
DHW THERMOSTAT
ANTI-CYCLE FUNCTION
RESET CH TIMERS
DHW THERMOSTAT
PREHEATING
PARAMETERS
INSTALLER
ANTI-CYCLE FUNCTION
This parameter allows you to change the
ANTI-CYCLE FUNCTION
,
regarding the delay time introduced for re-igniting the burner in the face
of an off due to the heating temperature being reached. The factory
setting for this parameter is 3 minutes and can be set to a value between
0 min and 20 min selecting the desired one with the
“up”
and
“down”
,
keys confirming the selection.
-
TIMER OFF CH
3
MIN
ANTI-CYCLE FUNCTION
RESET CH TIMERS
This parameter allows you to reset the REDUCED HEATING MAXIMUM
OUTPUT TIMING, during which the speed of the fan is limited to 75%
of the maximum heating output that has been set, and the ANTI-CYCLE
FUNCTION. The factory setting for this parameter is FUNCTION NON
ACTIVE, select FUNCTION ACTIVE using the keys
“up”
and
“down”
,
confirming the selection for resetting the timings.
FUNCTION NOT ACTIVE
RESET TIMERS CH
FUNCTION ACTIVE
INSTALLER
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
RESET CH TIMERS
INSTALLER
-
DOMESTIC HOT WATER THERMOSTAT
This parameter allows you to set the type of DOMESTIC HOT WATER
THERMOSTAT.
The factory setting for this parameter is RELATED, i.e. for domestic hot
water the boiler switches off at se5°C and restarts at setpoint
+4°C.
To select the ABSOLUTE values, where the boiler for domestic hot water
will still switch off at 65°C and restart at 63°C, use the keys
“up”
and
“down”
.
DHW THERMOSTAT
ABSOLUTE
INSTALLER
RELATED
DHW THERMOSTAT
RELATED
ABSOLUTE
INSTALLER
-
PREHEATING
Setting PREHEATING = 1 the boiler’s domestic hot water function
activates. This function keeps the water in the domestic hot water
exchanger hot, to reduce standby times when a request is made. When
the preheating function is enabled the symbol P comes on with a steady
light at the top with respect to the hot water icon. During burner ignition
following a preheating request, the symbol P starts flashing.
To deactivate the preheating function, set the parameter to PREHEATING
= 0, the symbol P switches off.
The function is not active when the boiler is OFF
.
TERMOSTATI SAN
PREHEATING
0
PREHEATING