Error
code
Diagnostic code
Meaning for the LMV37.4... system
Remedy
97
#
Error relay supervision
0
Safety relay contacts have welded or external power supply fed
to
safety relay
Test the contacts:
1. Unit connected to power: Fan output must be dead.
2.
Disconnect power: Disconnect fan. No resistive connection between fan
output and neutral conductor allowed.
If one of the 2 tests fails, release the unit since contacts have definit
ively welded
and safety can no longer be ensured.
98
#
Error relay supervision
2 Safety valve
3 Ignition transformer
4 Fuel valve 1
5 Fuel valve 2
6 Fuel valve 3
Relay does not pull in
Make a reset; if error occurs repeatedly, replace the unit
99
#
Internal error relay control
Make a reset; if error occurs repeatedly, replace the unit
3
Internal error relay control
Make a reset. If error occurs repeatedly, replace the unit
Software version V03.10: If error C:99 D:3 occurs during standardization of
the VSD, deactivate temporarily function Alarm in case of start pr
evention
(parameter 210 = 0, when using a release contact) or interrupt the
controller-ON
signal
100
#
Internal error relay control
Make a reset; if error occurs repeatedly, replace the unit
105
#
Internal error contact sampling
0 Pressure switch min
1
Pressure switch max
/ POC
2
Pressure switch valve
proving
3 Air pressure
4 Load controller open
5 Load controller on / off
6 Load controller close
7
Safety loop / Burner
flange
8 Safety valve
9 Ignition transformer
10 Fuel valve 1
11 Fuel valve 2
12 Fuel valve 3
13 Reset
Stuck-At failure
Can be caused by capacitive loads or supply of DC voltage to the
mains voltage
inputs. The diagnostic code indicates the input where the proble
m occurred
106
#
Internal error contact request
Make a reset; if error occurs repeatedly, replace the unit