26
Bentone
165 105 11-2
6.5 Replacement of electrical components
1.
Switch off the main power supply and disconnect the Euro plugs from
the burner.
2.
Note the connection of the existing component and remove.
3.
Install the new component using the same wiring as the existing
component or the specified alternative arrangement.
4.
Turn on the main power.
5.
Check the function of the new component.
6.
Start the burner and check/adjust combustion.
!
Before obtaining access to terminals,
all supply circuits must be disconnected.
!
When servicing/replacing components that affect combustion,
a flue gas analysis and soot test shall be carried out on the installation.