21
Bentone
5.6 Example of basic settings
This is an example of nozzle selection and air/insert setting.
Selection of output and connection between the different power stages must
be selected and adjusted so that the system achieves good functionality.
Example - Basic settings B 45i A2.2H
Values can be determined from diagrams for air damper and insert setting
values, (see Technical data).
The different program steps are described in the LMV chapter.
Insert setting
Step 1
27
Step 2
27
Air setting
Step 1
5
Step 2
8
Example - Nozzle selection B 45i A2.2H
Burner output
418 kW
Pump pressure
14 bar
Nozzle selection according to table, (see Technical data).
Step 1
62%
261 kW
5.0 Gph
Step 2
38%
157 kW
3.0 Gph