background image

2.5 Two pipe system  

 

This is used where the oil storage tank is lower than 
the pump. 
 Access for the fuel feed to the burner should be via 
a suitable tapping made in the top of the tank, and 
the fuel feed pipe should extend to not less than 
100mm above the bottom of the tank.  
A none return valve with a metal to metal seat 
should be fitted, especially if the return pipe work is 
terminated at a level above the draw off tube.  
The non return valve must be removable for service 
and maintenance purposes, and the return pipe from 
the pump must therefore be extended down into the 
tank to the same level as the suction pipe. 
 The presence of a tamper proof isolating valve fitted 
within the return pipe is only required if there is a 
risk that oil will siphon out of the tank if the return 
pipe is disconnected at the pump during 
maintenance or servicing and if the none return 
valve has been omitted. 
 

2.6 Pipe work and fittings  

 

Caution 

 

Galvanised pipe work and fittings must not be used. 
All joints must be sealed properly, if necessary using 
PTFE tape or other approved sealing media. 
The pipe work must be effectively sealed so as to 
prevent the ingress of air. 
It is advisable to check all pipe work prior to 
installation to ensure that there is no loose debris or 
scale present.  
Black iron pipes can be hammered to assist in the 
removal of these contaminants. 
 

Note 

 

The oil feed to each heater must be fitted with a fire 
check valve and isolating valve. 
The fire check valve must be operated by way of a 
fusible link positioned so that it is above the burner. 

 

2.7 Oil Installation/connection  

 

The oil tank must be positioned so that there is a fall 
of 7.5mm (+/- 2.5mm) for every 30mm away from 
the outlet and towards the sludge/drain valve, which 
must be sited at the lowest point in the tank. If the 
tank is positioned on supports then there must be an 
adequate protective layer between tank and support 

to prevent damage or deterioration through 
corrosion 
 It is strongly suggested that reference is made to 
BS 5410 ; part 2 ; 1978.  
It is also suggested that the installer is familiar with 
the detail and requirements contained within 
sections 2.1 through to section 2.6 of this manual 
prior to commencing installation. 
 

Warning 

 

Prolonged exposure and contact with Gas Oil can 
result in the natural oils being removed from the 
skin, sensitisation can result in dermatitis. 
 

Always ensure that the appropriate personal 
protective equipment is used

 

2.8 Electrical supply 

  

Wiring external to the cabinet heater must be 
installed in accordance with any local, national, and 
European regulations, as well as meeting the 
appropriate requirements of IEE regulations. 
 
The means of connection to the main electrical 
supply must allow for complete electrical isolation of 
the heater, furthermore, in the case of a unit wired 
for a three phase supply, the supply should only be 
used to serve the heater itself and no other plant or 
equipment. 
 

Warning 

Ensure that the electric and oil supplies are turned 
off before any electrical work is carried out on the 
heater.  
Ensure that wiring cannot make contact with any 
surfaces liable to be subject to high temperatures or 
where the insulation of the wiring could be impaired 
as a result of such contact. 
 

All Benson cabinet heaters must be earthed

 

Caution  

The main electrical supply must not be switched off 
or disconnected as a method for stopping the 
heater, the exception to this is in an emergency, or 
during servicing, when the heat exchanger has been 
allowed to cool sufficiently to prevent any damage 
from occurring. 
 
Claims for damage will not be considered if they 

Содержание MH300

Страница 1: ...BENSON MH300 OIL FIRED MARQUEE HEATER I N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S...

Страница 2: ......

Страница 3: ...work Fittings 8 2 7 Oil installation and Connection 8 2 8 Electrical Supply 8 2 9 Air Supply 9 2 10 Air Distribution 10 2 11 Flue System 11 3 0 Installation 11 3 1 Electrical installation Connection...

Страница 4: ...on Heating to ensure that they are familiar with the appropriate information manuals supplied by the manufacturer and that they are suitably aware of the purpose of the manuals and the safety instruct...

Страница 5: ...Warning Unauthorised modifications to the appliance or departure from the manufacturers guidance on intended use or installation contrary to the manufacturers recommendations may constitute a hazard N...

Страница 6: ...n to enable processing to take place 1 Heater model 2 Heater serial number 3 Order reference date of order together with full installation details name and address 4 Details or symptoms of fault Fault...

Страница 7: ...ll below the cold filter plugging point cfpp in this country and with class D fuel also referred to as gas oil The critical temperature is 4oC for this summer grade The cfpp critical temperature for t...

Страница 8: ...let and towards the sludge drain valve which must be sited at the lowest point in the tank If the tank is positioned on supports then there must be an adequate protective layer between tank and suppor...

Страница 9: ...space being heated And The building design air change rate is less than 0 5 air changes per hour and the volume of the space is greater than 4 7m3 per kilowatt then low level ventilation is required...

Страница 10: ...06m3 h per kW of rated heat input Mechanical ventilation systems where fitted must be provided with safety interlocks to prevent heater operation in case of air flow failure 2 9 3 Ventilation Openings...

Страница 11: ...stant to internal and external corrosion and be capable of withstanding the stresses and loadings associated with normal use 3 0 Installation 3 1 Electrical Installation Connection Benson MH 300 cabin...

Страница 12: ...rs undergo a rigorous test programme prior to being dispatched whilst such a programme does involve pre commissioning and setting up the heater to operate efficiently and well within its designed oper...

Страница 13: ...position for heater on off switch f Check for the following burner sequence Interval Operand 1 5s Combustion air damper actuated burner fan motor initiates purge cycle 2 15s Solenoid valve opens ignit...

Страница 14: ...settings should be only very finely adjusted to achieve a CO2 reading of 12 5 0 5 Note ii The gross efficiency must be approximately 80 Note iii All Heaters are test fired and pre commissioned as par...

Страница 15: ...ding environment and the need for regular servicing carried out by competent and qualified persons Caution After approximately 100 hours of running the tension of the fan belts must be checked to ensu...

Страница 16: ...Fan Motor Remove access panel Dust and other foreign matter should be cleaned by blowing over with compressed air and through the use of a soft bristle brush and cloth Solvent wipes may be used to re...

Страница 17: ...ne belt contains more slack than its accompanying belts then all the belts on the unit must be replaced again using a common batch code Replacement and tensioning is carried out as follows Note The ma...

Страница 18: ...ecked to ensure that they are secure and free from corrosion Terminals and connections should also be checked to ensure that no stray strands are bridging terminals Electrical continuity should also b...

Страница 19: ...out Occurs Fuel Feed Incorrect Check that the Oil Pressure is correct Check that Head of Gravity is Sufficient Check that the suction Lift is not too great two pipe system Check that the Bypass Plug i...

Страница 20: ...Line Check Fuel Pressure Check Nozzle Check Filter Check Fuel Lines Check Valves Burner gives a smokey flame Poor Combustion Insufficient Combustion Air Inadequate Flue Draught Check Oil Pressure Che...

Страница 21: ...ockout Warm Air Short Circuit Adjust Warm Air Discharge and Cool Air Inlet Accordingly Check for High Resistance Check Outlet Grilles are not shut or Check Filter is Clear Insufficient Air Flow over t...

Страница 22: ...Wiring Diagram 20 49 146...

Страница 23: ...tic pressure full load pa 750 Discharge velocity full load M s 19 5 Noise level full load Dba 1 m 90 Heat Input part load kW 225 Heat output part load kW 180 Nett efficiency part load 90 5 Gross effic...

Страница 24: ...nnection size Bsp 1 4 Fuel specification 35 sec Head setting 5 Air shutter Hi Lo 70 28 Electrical supply V Hz Ph 415 50 3 Fuse Size Amps 6 Maximum running current Amps 16 Flue diameter mm 225 Overheat...

Страница 25: ...magnetic Compatibility BS EN 50165 1995 Safety of Electrical Equipment BS 5854 1980 Code of Practice Flues Flue Structures BS 799 Part 5 1987 Oil Burning Equipment oil tanks OFTEC OFS T 100 Polyethyle...

Страница 26: ...Benson Heating Ludlow Road Knighton Powys LD7 1LP Telephone 44 0 1547 528534 Facsimile 44 0 1547 520399 Email information bensonheating co uk www bensonheating com...

Отзывы: