background image

 High Level (Outlet) 

 
For heaters with a rated input of less than 
60 kW — 4.5 cm

per kW of heat input 

 
For heaters with a rated input of more than 60 kW 
— 270 cm

2

 plus for each kW of rated input over the 

60 kW threshold an additional 2.25 cm

2

 

 
Alternatively mechanical input (not extract) 
ventilation may be used in association with either 
mechanical or natural extract and with a ventilation 
flow rate of 2.16m

3

/h per kW of total rated input. 

 
Mechanical ventilation systems where fitted must 
be provided with safety interlocks to prevent heater 
operation in case of air flow failure  
 
Where the combustion air intake 

is not ducted to 

atmosphere 

heater installed in flue only 

configuration  then ventilation can be via a 
permanent ventilation opening  / grille situated at 
both Low level (Inlet) and high Level (Outlet) and 
with the free area of such grilles as :-  
  

Low level (Inlet) 

 
For heaters with a rated input of less than 
60 kW — 9.0 cm

2

 per kW of heat input 

 
For heaters with a rated input of more than 60 kW 
— 540 cm

2

 plus for each kW of rated input over the 

60 kW threshold an additional 4.5 cm

2

 

 

 High Level (Outlet) 

 
For heaters with a rated input of less than 
60 kW — 4.5 cm

per kW of heat input 

 
For heaters with a rated input of more than 60 kW 
— 270 cm

2

 plus for each kW of rated input over the 

60 kW threshold an additional 2.25 cm

2

 

 
Alternatively mechanical input (not extract)  
ventilation may be used in association with either 
mechanical or natural extract , and with a 
ventilation flow rate of 3.24m

3

/h per kW of total 

rated input       
 
Where mechanical extract is used to complement  

the above then the extract rate shall be 2.06m

3

/h 

per kW of rated heat input  
 
Mechanical ventilation systems where fitted must 
be provided with safety interlocks to prevent heater 
operation in case of air flow failure  
 

2.9.3 Ventilation Openings and Grilles  

Ventilation openings and grilles must communicate 
directly with the outside air, be of  negligible 
resistance and shall be sited so that they cannot 
easily be blocked of flooded

 

 
Caution 

Additionally, an automatic control interlocked to the 
burner must be fitted to ensure burner shutdown in 
the event of airflow failure or restriction.

 

 
2.10 Air distribution system 

 
All materials used within the construction of the 
delivery and return air ducts must not represent a 
fire hazard and should be made from thermally 
inert materials.  
The selection of materials must take account of the 
environment into which the heater and its air 
delivery system is expected to work, it must also 
take account of the stresses and loadings placed 
upon it during its normal working life. 
Where interjoist spaces are used to route ducting 
these must be lined with fire resistant insulation 
material. 
 
In installations where forced recirculation is a 
feature, a full and unobstructed return air path to 
the heater(s) must be provided, with return air 
grilles connected by ducting directly to the return 
air inlet on the heater.  
The limit for recirculation should not be greater 
than 85% re-circulated air to 15% fresh air. 
  
If the inlet air is ducted to the outside, then the 
lowest edge of the inlet air duct must be at least 
500mm above the outside floor or ground level, it 
must also be fitted with an access point(s) to allow 
for cleaning and servicing. 
The openings in the structure through which the 
ductwork passes must be of fire resistant material 
and constructed to prevent the likelihood of any fire 
from spreading. 

Содержание MH300

Страница 1: ...BENSON MH300 OIL FIRED MARQUEE HEATER I N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S...

Страница 2: ......

Страница 3: ...work Fittings 8 2 7 Oil installation and Connection 8 2 8 Electrical Supply 8 2 9 Air Supply 9 2 10 Air Distribution 10 2 11 Flue System 11 3 0 Installation 11 3 1 Electrical installation Connection...

Страница 4: ...on Heating to ensure that they are familiar with the appropriate information manuals supplied by the manufacturer and that they are suitably aware of the purpose of the manuals and the safety instruct...

Страница 5: ...Warning Unauthorised modifications to the appliance or departure from the manufacturers guidance on intended use or installation contrary to the manufacturers recommendations may constitute a hazard N...

Страница 6: ...n to enable processing to take place 1 Heater model 2 Heater serial number 3 Order reference date of order together with full installation details name and address 4 Details or symptoms of fault Fault...

Страница 7: ...ll below the cold filter plugging point cfpp in this country and with class D fuel also referred to as gas oil The critical temperature is 4oC for this summer grade The cfpp critical temperature for t...

Страница 8: ...let and towards the sludge drain valve which must be sited at the lowest point in the tank If the tank is positioned on supports then there must be an adequate protective layer between tank and suppor...

Страница 9: ...space being heated And The building design air change rate is less than 0 5 air changes per hour and the volume of the space is greater than 4 7m3 per kilowatt then low level ventilation is required...

Страница 10: ...06m3 h per kW of rated heat input Mechanical ventilation systems where fitted must be provided with safety interlocks to prevent heater operation in case of air flow failure 2 9 3 Ventilation Openings...

Страница 11: ...stant to internal and external corrosion and be capable of withstanding the stresses and loadings associated with normal use 3 0 Installation 3 1 Electrical Installation Connection Benson MH 300 cabin...

Страница 12: ...rs undergo a rigorous test programme prior to being dispatched whilst such a programme does involve pre commissioning and setting up the heater to operate efficiently and well within its designed oper...

Страница 13: ...position for heater on off switch f Check for the following burner sequence Interval Operand 1 5s Combustion air damper actuated burner fan motor initiates purge cycle 2 15s Solenoid valve opens ignit...

Страница 14: ...settings should be only very finely adjusted to achieve a CO2 reading of 12 5 0 5 Note ii The gross efficiency must be approximately 80 Note iii All Heaters are test fired and pre commissioned as par...

Страница 15: ...ding environment and the need for regular servicing carried out by competent and qualified persons Caution After approximately 100 hours of running the tension of the fan belts must be checked to ensu...

Страница 16: ...Fan Motor Remove access panel Dust and other foreign matter should be cleaned by blowing over with compressed air and through the use of a soft bristle brush and cloth Solvent wipes may be used to re...

Страница 17: ...ne belt contains more slack than its accompanying belts then all the belts on the unit must be replaced again using a common batch code Replacement and tensioning is carried out as follows Note The ma...

Страница 18: ...ecked to ensure that they are secure and free from corrosion Terminals and connections should also be checked to ensure that no stray strands are bridging terminals Electrical continuity should also b...

Страница 19: ...out Occurs Fuel Feed Incorrect Check that the Oil Pressure is correct Check that Head of Gravity is Sufficient Check that the suction Lift is not too great two pipe system Check that the Bypass Plug i...

Страница 20: ...Line Check Fuel Pressure Check Nozzle Check Filter Check Fuel Lines Check Valves Burner gives a smokey flame Poor Combustion Insufficient Combustion Air Inadequate Flue Draught Check Oil Pressure Che...

Страница 21: ...ockout Warm Air Short Circuit Adjust Warm Air Discharge and Cool Air Inlet Accordingly Check for High Resistance Check Outlet Grilles are not shut or Check Filter is Clear Insufficient Air Flow over t...

Страница 22: ...Wiring Diagram 20 49 146...

Страница 23: ...tic pressure full load pa 750 Discharge velocity full load M s 19 5 Noise level full load Dba 1 m 90 Heat Input part load kW 225 Heat output part load kW 180 Nett efficiency part load 90 5 Gross effic...

Страница 24: ...nnection size Bsp 1 4 Fuel specification 35 sec Head setting 5 Air shutter Hi Lo 70 28 Electrical supply V Hz Ph 415 50 3 Fuse Size Amps 6 Maximum running current Amps 16 Flue diameter mm 225 Overheat...

Страница 25: ...magnetic Compatibility BS EN 50165 1995 Safety of Electrical Equipment BS 5854 1980 Code of Practice Flues Flue Structures BS 799 Part 5 1987 Oil Burning Equipment oil tanks OFTEC OFS T 100 Polyethyle...

Страница 26: ...Benson Heating Ludlow Road Knighton Powys LD7 1LP Telephone 44 0 1547 528534 Facsimile 44 0 1547 520399 Email information bensonheating co uk www bensonheating com...

Отзывы: