The location must also allow for adequate 
clearance for the air supply, return air circulation, oil 
supply, electrical supply, whilst also providing good 
and safe working 

access. 

 
Any combustible material adjacent to the heater or 
flue system must be so placed or shielded so that 
its surface temperature does not exceed 65

o

C. 

 

Warning 
 

TRANSPORTATION

 

The heater should be kept in a 

HORIZONTAL

 

position at all times when being transported by 
fork lift truck or other mechanical devices   

 

2.1 Fuel supply - general 

 

 
The Benson MH 300 of oil fired heater are all 
manufactured and pre-set for use with 35 second 
gas oil delivered to the burner via a suitable piped 
system from the oil storage tank. 
 
The constraints of the application will, to a large 
extent, determine whether it is preferable to use a 
single pipe gravity feed system, or whether the two 
pipe pumped system is more appropriate. 
  
 All pipe work must be constructed and installed so 
that it does not permit the ingress of air. 
The construction, size, and position of the oil 
storage tank must take account of the current 
regulations, as well as suiting the requirements of 
the installation. 

 
Caution 

 

On pumped systems always check that the pump is 
correctly set up prior to running, and always ensure 
that valves are open allowing a free flow of oil 
through the system. 
 

2.2 Fuel  

 

In order to promote trouble free operating it is 
necessary that the oil within the storage tank and 
oil line does not fall below the cold filter plugging 
point (cfpp), in this country and with class D fuel 
(also referred to as gas oil). The critical 
temperature is -4oC for this summer grade. 
The cfpp critical temperature for the winter grade is 

-12oC. 
 If summer grade fuel is stored for winter use in 
areas prone to severe frosts and low temperatures 
it will be necessary to insulate or even heat the 
supply tank and pipe work. 
 
 

Warning        

      

The pump pressure must not exceed a maximum of 
0.4 bar, this is because beyond this point gas is 
liberated from the oil. 
 

2.3 Storage tank  

 
It is advisable to leave the tank unpainted on the 
inside, but to paint the outside with a proprietary 
grade of anti-corrosive paint. 

A galvanised or open topped tank is strictly not 
allowed. 

 
If a medium density polyethylene oil tank is to be 
used then it must be OFTEC certified to OFS T-
100. 
Local, National, European and Fire regulations 
must also be complied with. 
 

2.4 Single pipe system (gravity feed)  

 

For installations where the oil tank is 300mm or 
more above the level of the fuel pump the principle 
of gravity feed may be used.  
The draw off point for the supply to the burner must 
not be positioned any lower than 100mm above the 
bottom of the tank.  
Where a return valve is fitted this must be tamper 
proof to prevent inadvertent operation. 

 

Caution  

If the valve is closed when the pump is running the 
oil pressure can be increased sufficiently so as to 
cause damage to the seals within the pump. 
 
The return oil should preferably be discharged 
through an elbow onto a tank plate situated within 
the tank, this should be positioned so as not to 
introduce air or air bubbles into the draw off pipe. 
 
 
 
 

Содержание MH300

Страница 1: ...BENSON MH300 OIL FIRED MARQUEE HEATER I N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S...

Страница 2: ......

Страница 3: ...work Fittings 8 2 7 Oil installation and Connection 8 2 8 Electrical Supply 8 2 9 Air Supply 9 2 10 Air Distribution 10 2 11 Flue System 11 3 0 Installation 11 3 1 Electrical installation Connection...

Страница 4: ...on Heating to ensure that they are familiar with the appropriate information manuals supplied by the manufacturer and that they are suitably aware of the purpose of the manuals and the safety instruct...

Страница 5: ...Warning Unauthorised modifications to the appliance or departure from the manufacturers guidance on intended use or installation contrary to the manufacturers recommendations may constitute a hazard N...

Страница 6: ...n to enable processing to take place 1 Heater model 2 Heater serial number 3 Order reference date of order together with full installation details name and address 4 Details or symptoms of fault Fault...

Страница 7: ...ll below the cold filter plugging point cfpp in this country and with class D fuel also referred to as gas oil The critical temperature is 4oC for this summer grade The cfpp critical temperature for t...

Страница 8: ...let and towards the sludge drain valve which must be sited at the lowest point in the tank If the tank is positioned on supports then there must be an adequate protective layer between tank and suppor...

Страница 9: ...space being heated And The building design air change rate is less than 0 5 air changes per hour and the volume of the space is greater than 4 7m3 per kilowatt then low level ventilation is required...

Страница 10: ...06m3 h per kW of rated heat input Mechanical ventilation systems where fitted must be provided with safety interlocks to prevent heater operation in case of air flow failure 2 9 3 Ventilation Openings...

Страница 11: ...stant to internal and external corrosion and be capable of withstanding the stresses and loadings associated with normal use 3 0 Installation 3 1 Electrical Installation Connection Benson MH 300 cabin...

Страница 12: ...rs undergo a rigorous test programme prior to being dispatched whilst such a programme does involve pre commissioning and setting up the heater to operate efficiently and well within its designed oper...

Страница 13: ...position for heater on off switch f Check for the following burner sequence Interval Operand 1 5s Combustion air damper actuated burner fan motor initiates purge cycle 2 15s Solenoid valve opens ignit...

Страница 14: ...settings should be only very finely adjusted to achieve a CO2 reading of 12 5 0 5 Note ii The gross efficiency must be approximately 80 Note iii All Heaters are test fired and pre commissioned as par...

Страница 15: ...ding environment and the need for regular servicing carried out by competent and qualified persons Caution After approximately 100 hours of running the tension of the fan belts must be checked to ensu...

Страница 16: ...Fan Motor Remove access panel Dust and other foreign matter should be cleaned by blowing over with compressed air and through the use of a soft bristle brush and cloth Solvent wipes may be used to re...

Страница 17: ...ne belt contains more slack than its accompanying belts then all the belts on the unit must be replaced again using a common batch code Replacement and tensioning is carried out as follows Note The ma...

Страница 18: ...ecked to ensure that they are secure and free from corrosion Terminals and connections should also be checked to ensure that no stray strands are bridging terminals Electrical continuity should also b...

Страница 19: ...out Occurs Fuel Feed Incorrect Check that the Oil Pressure is correct Check that Head of Gravity is Sufficient Check that the suction Lift is not too great two pipe system Check that the Bypass Plug i...

Страница 20: ...Line Check Fuel Pressure Check Nozzle Check Filter Check Fuel Lines Check Valves Burner gives a smokey flame Poor Combustion Insufficient Combustion Air Inadequate Flue Draught Check Oil Pressure Che...

Страница 21: ...ockout Warm Air Short Circuit Adjust Warm Air Discharge and Cool Air Inlet Accordingly Check for High Resistance Check Outlet Grilles are not shut or Check Filter is Clear Insufficient Air Flow over t...

Страница 22: ...Wiring Diagram 20 49 146...

Страница 23: ...tic pressure full load pa 750 Discharge velocity full load M s 19 5 Noise level full load Dba 1 m 90 Heat Input part load kW 225 Heat output part load kW 180 Nett efficiency part load 90 5 Gross effic...

Страница 24: ...nnection size Bsp 1 4 Fuel specification 35 sec Head setting 5 Air shutter Hi Lo 70 28 Electrical supply V Hz Ph 415 50 3 Fuse Size Amps 6 Maximum running current Amps 16 Flue diameter mm 225 Overheat...

Страница 25: ...magnetic Compatibility BS EN 50165 1995 Safety of Electrical Equipment BS 5854 1980 Code of Practice Flues Flue Structures BS 799 Part 5 1987 Oil Burning Equipment oil tanks OFTEC OFS T 100 Polyethyle...

Страница 26: ...Benson Heating Ludlow Road Knighton Powys LD7 1LP Telephone 44 0 1547 528534 Facsimile 44 0 1547 520399 Email information bensonheating co uk www bensonheating com...

Отзывы: