background image

(f) Fit the eccentric collar and engage the 
cams. 
(g) Tighten initially by rotating, and then by 
tapping in the direction of the fan rotation. 
(h) Replace fasteners and secure. 
(i) Turn by hand to ensure free fan rotation. 
 

Pulleys 

Check pulleys for alignment using a straight 
edge, if necessary reposition either or both of 
the pulleys and the fan motor.  
Check for excessive wear within the root and 
sides of the grooves, and check for any other 
signs of wear or damage, if necessary replace 
the pulley as follows. 
 
(a) Release tension on belts and remove. 
(b) Release the taper locks by slackening the 
securing screws by several complete turns. 
 
(c) Fully remove one screw from the taper lock, 
and having oiled it, insert into the threaded 
jacking point. 
(d) Tighten screw until the taperlock is free. 
(e) Remove taperlock and pulley. 
(f) Fit taperlock in new pulley, and provisionally 
position on the shaft. 
(g) Remove the screw from the jacking point, 
and tighten both screws in their clamping 
points until the pulley can just be moved on the 
shaft by hand. 
(h) Align pulleys using a straight edge, and by 
gradual alternate tightening of the screws 
clamp in position. 
(i) Refit belts and check for the correct amount 
of tension. 
 

Fan Belts 

Check belts for signs of wear. 
Frayed or split belts must be replaced using 
belts with a common batch code. 
Belt tension must be checked, and if on multi-
belt units it is found that one belt contains 
more slack than its accompanying belts, then 
all the belts on the unit must be replaced, 
again using a common batch code. 
Replacement and tensioning is carried out as 
follows. 
 

Note  

The maximum displacement at the mid point of 
the top edge of the belt must not be greater 
than 16mm per metre of span, when a force of 
3kg is applied in a plane perpendicular to the 
belt. 
 
(a) Loosen fan motor securing bolts on 
chassis. 
(b) Loosen fan motor slide adjustment bolt. 
(c) Slide fan towards fan to slacken belts. 
(d) Replace belts, pull fan motor away from fan 
until belts are tight. 
(e) Tighten adjustment bolt to hold motor. 
(f) Tighten fan securing bolts ensuring that the 
fan is square and the pulleys aligned. 
(g) Check belt tension, making final 
adjustments as necessary. 
(h) Tighten and clamp fasteners to hold fan 
motor in position. 
 

Heat Exchanger 

 
The heat exchanger requires a visual 
inspection at least once per year, this should 
be accompanied by cleaning. It is 
recommended that a flue brush and vacuum 
cleaner be used to facilitate this. 
Access to the heat exchanger is gained 
through the removal of the Front panel and 
heat shield. 
 
Servicing and cleaning should be performed as 
follows. 
 
(a) Remove brass nuts and cover from heat 
exchanger end assembly to expose heat 
exchanger tubes. 
 
(b) Remove any accumulated deposits from 
the tubes by pushing through the full length 
with a flue brush. 
 
(c) The flue brush should be withdrawn so as 
to pull any deposits back into the bottom of the 
flue box where they can then be removed by 
using a vacuum cleaner. 
 
 
 
(d) Particular attention should be paid to the 

Содержание MH300

Страница 1: ...BENSON MH300 OIL FIRED MARQUEE HEATER I N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S...

Страница 2: ......

Страница 3: ...work Fittings 8 2 7 Oil installation and Connection 8 2 8 Electrical Supply 8 2 9 Air Supply 9 2 10 Air Distribution 10 2 11 Flue System 11 3 0 Installation 11 3 1 Electrical installation Connection...

Страница 4: ...on Heating to ensure that they are familiar with the appropriate information manuals supplied by the manufacturer and that they are suitably aware of the purpose of the manuals and the safety instruct...

Страница 5: ...Warning Unauthorised modifications to the appliance or departure from the manufacturers guidance on intended use or installation contrary to the manufacturers recommendations may constitute a hazard N...

Страница 6: ...n to enable processing to take place 1 Heater model 2 Heater serial number 3 Order reference date of order together with full installation details name and address 4 Details or symptoms of fault Fault...

Страница 7: ...ll below the cold filter plugging point cfpp in this country and with class D fuel also referred to as gas oil The critical temperature is 4oC for this summer grade The cfpp critical temperature for t...

Страница 8: ...let and towards the sludge drain valve which must be sited at the lowest point in the tank If the tank is positioned on supports then there must be an adequate protective layer between tank and suppor...

Страница 9: ...space being heated And The building design air change rate is less than 0 5 air changes per hour and the volume of the space is greater than 4 7m3 per kilowatt then low level ventilation is required...

Страница 10: ...06m3 h per kW of rated heat input Mechanical ventilation systems where fitted must be provided with safety interlocks to prevent heater operation in case of air flow failure 2 9 3 Ventilation Openings...

Страница 11: ...stant to internal and external corrosion and be capable of withstanding the stresses and loadings associated with normal use 3 0 Installation 3 1 Electrical Installation Connection Benson MH 300 cabin...

Страница 12: ...rs undergo a rigorous test programme prior to being dispatched whilst such a programme does involve pre commissioning and setting up the heater to operate efficiently and well within its designed oper...

Страница 13: ...position for heater on off switch f Check for the following burner sequence Interval Operand 1 5s Combustion air damper actuated burner fan motor initiates purge cycle 2 15s Solenoid valve opens ignit...

Страница 14: ...settings should be only very finely adjusted to achieve a CO2 reading of 12 5 0 5 Note ii The gross efficiency must be approximately 80 Note iii All Heaters are test fired and pre commissioned as par...

Страница 15: ...ding environment and the need for regular servicing carried out by competent and qualified persons Caution After approximately 100 hours of running the tension of the fan belts must be checked to ensu...

Страница 16: ...Fan Motor Remove access panel Dust and other foreign matter should be cleaned by blowing over with compressed air and through the use of a soft bristle brush and cloth Solvent wipes may be used to re...

Страница 17: ...ne belt contains more slack than its accompanying belts then all the belts on the unit must be replaced again using a common batch code Replacement and tensioning is carried out as follows Note The ma...

Страница 18: ...ecked to ensure that they are secure and free from corrosion Terminals and connections should also be checked to ensure that no stray strands are bridging terminals Electrical continuity should also b...

Страница 19: ...out Occurs Fuel Feed Incorrect Check that the Oil Pressure is correct Check that Head of Gravity is Sufficient Check that the suction Lift is not too great two pipe system Check that the Bypass Plug i...

Страница 20: ...Line Check Fuel Pressure Check Nozzle Check Filter Check Fuel Lines Check Valves Burner gives a smokey flame Poor Combustion Insufficient Combustion Air Inadequate Flue Draught Check Oil Pressure Che...

Страница 21: ...ockout Warm Air Short Circuit Adjust Warm Air Discharge and Cool Air Inlet Accordingly Check for High Resistance Check Outlet Grilles are not shut or Check Filter is Clear Insufficient Air Flow over t...

Страница 22: ...Wiring Diagram 20 49 146...

Страница 23: ...tic pressure full load pa 750 Discharge velocity full load M s 19 5 Noise level full load Dba 1 m 90 Heat Input part load kW 225 Heat output part load kW 180 Nett efficiency part load 90 5 Gross effic...

Страница 24: ...nnection size Bsp 1 4 Fuel specification 35 sec Head setting 5 Air shutter Hi Lo 70 28 Electrical supply V Hz Ph 415 50 3 Fuse Size Amps 6 Maximum running current Amps 16 Flue diameter mm 225 Overheat...

Страница 25: ...magnetic Compatibility BS EN 50165 1995 Safety of Electrical Equipment BS 5854 1980 Code of Practice Flues Flue Structures BS 799 Part 5 1987 Oil Burning Equipment oil tanks OFTEC OFS T 100 Polyethyle...

Страница 26: ...Benson Heating Ludlow Road Knighton Powys LD7 1LP Telephone 44 0 1547 528534 Facsimile 44 0 1547 520399 Email information bensonheating co uk www bensonheating com...

Отзывы: