Internal components and modules
81
TM800_D00165_00_M_XXEN/06.2015
Connections:
10.3.3 Technical data BI71S
Overvoltage category ........................................................................................................................................................ III
Pollution degree ................................................................................................................................................................. 2
Rated insulation voltage..............................................................................................................................................250 V
Safe separation between the connections..............(1…16), (11…14), (21…24), (31…34, (41…44), (51…54)
Voltage test according to IEC 61010-1 (basic insulation/protective separation) ....................................2.21 kV/3.51 kV
Supply:
Nominal voltage ....................................................................................................................................... DC 24 V, AC 24 V
Maximum current consumption............................................................................................................................. 110 mA
Relay contacts:
Maximum current...............................................................................................................8 A at AC 250 V/8 A at DC 24 V
Maximum switching load ...............................................................................................................AC 2000 VA/DC 192 W
Maximum switching voltage
Minimum switching load.......................................................................................................................... 10 mA at DC 5 V
EMC..................................................................................................................................... IEC 61000-6-2, IEC 61000-6-3
Operating temperature ..........................................................................................................................-25 °C … +55 °C
10.3.4 Ordering information BI71S
1
U
s
: DC +24 V or AC 24 V 50/60 Hz
2
U
s
: DC 0 V or AC 24 V 50/60 Hz
3
Lamp test
4
Lamp test
5
Output: GND
6
Output: DC +24 V
7
LED 5, GND
8
LED 5, +
9
LED 4, GND
10
LED 4, +
11
LED 3, GND
12
LED 3, +
13
LED 2, GND
14
LED 2, +
15
LED 1, GND
16
LED 1, +
11, 12, 14
changeover contact K1
21, 22, 24
changeover contact K2
31, 32, 34
changeover contact K3
41, 42, 44
changeover contact K4
51, 52, 54
changeover contact K5
Type Description
Art.
No.
BI71S
Operating and display module
with five illuminated pushbuttons, UC 24
V, for TM panels, new version with SMD
LEDs
B92024071