Installation and connection
36
TM800_D00165_00_M_XXEN/06.2015
Explanatory note to the digital inputs (*)
Alarm messages from digital inputs on TM/MK800 are always displayed on the device itself regard-
less of whether an individual message has been programmed or not (Exception:
channel is deactivated).
An entry into the alarm address table is not required.
If no individual message is programmed, the standard text will be displayed.
An alarm message can also be programmed to be displayed without text/LED/buzzer (
silent
message
).
Note: Flashing alarm messages are not allowed!
In principle, all alarm messages are stored in the history memory (Exception: channel is deactivated):
If no individual message is programmed, the standard text will be displayed resp. will be stored
in the history memory.
If the message has been programmed without a text (silent message), its source (DigIn resp.
address and channel No.) will be stored in the history memory (no individual text possible!).
Test messages are only stored in the history memory of the device that triggered the message.
Transmission via BMS bus:
All alarm messages are actively sent (i.e. as a new message) via the external or internal BMS.
Operating messages are actively sent via the external BMS bus and are not stored in the history
memory.
Note: Flashing messages must be avoided, where possible, and on no account be sent via the
int./ext. BMS bus!
The first 16 digital inputs can be configured as "flashing" and in this case are not signalled via
the external BMS. This is only permissible for messages with a flashing frequency of 0.5 Hz!
Inputs that are assigned to operating messages or switching commands are not displayed with a text
message or stored into the history memory.