Installation and connection
32
TM800_D00165_00_M_XXEN/06.2015
On the external bus, the Master function can be cyclically passed from one address to the next
higher one.
4.3 Examples for connection and address assignment
Example Devices on the internal bus
Changeover and monitoring module UMC107E-… with alarm indicator and operator panel TM800 and
3 alarm indicator and test combinations MK2430. All components are connected to the TM800 via the in-
ternal RS-485 interface.
The addresses are consecutively assigned to additional TM800 alarm indicator
and operator panels (2, 3 etc.). Only when there are no gaps between the ad-
dresses, reliable function can be ensured.
All devices on the external bus must be equipped with compatible software ver-
sions (see chapter "3.3.6 ").
All devices must be set to the same baud rate.
CAUTION