Menu mode: Operation and setting
68
TM800_D00165_00_M_XXEN/06.2015
EDS system stop
Stops the EDS4xx-12 and PGH47x from continuous operation. If you exit the
menu, "EDS" will appear in the last line of the standard display until the cur-
rent measurement cycle finishes.
*
Other abbreviations that might appear in the last line of the display:
EDSa
Automatic mode: Insulation fault location has been started by e.g.
ISOMETER®, ATICS® or isoMED427P on PGH47x.
EDSs
Single mode A single run has been started by IN2 on PGH471.
8.4.5.4
Control menu 4: Test communication
Testing the communication via the BMS bus. For this purpose, an error message is simulated on a
digital input. This fault message is sent to evaluating devices (such as MK…, TM…, SMO…) via the
BMS bus. Check that these devices are responding to the fault message as requested.
Channel 3
Setting of the channel whose message is to be activated.
8.4.5.5
Control menu Reset mode
Set whether the reset command should have an effect on the internal BMS bus only or also on the
external bus. Setting possibilities
– internally only
– internally and externally
8.4.6
Menu 6: External devices
This menu is used to set and control external devices. Functions include for example displaying in-
formation about connected devices (address, software version, device type) or continuous display-
ing a channel on a connected evaluator.
Select the BMS bus to which the external device is connected.
Internal interface
Devices connected to the internal bus of this TM800 can be displayed and
adjusted.
External interface
Devices connected to the external bus of this TM800 can be displayed and
adjusted. If other Bender devices utilising an internal bus (TM…, MK…) are
addressed via the external bus, also the devices connected to this internal
bus can be displayed and adjusted.
Devices which can be parameterised:
EDS46x, EDS47x, EDS49x,
RCMS460, RCMS470, RCMS490
The device connected to the selected bus will be displayed. Select the address of the external device
to be displayed (e.g. EDS4xx-12 or RCMS4xx-12).
1.Exit
2.Channel: 3
-Test communication-
1. Exit
2. Internal interface
3. External interface