![Bender ISOMETER isoHV525 Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/bender/isometer-isohv525/isometer-isohv525_manual_2731666046.webp)
Technical data
46
isoHV525_D00297_04_M_XXEN/05.2018
Operating uncertainty ............................................................................................................................. ±5 %, at least ±5 V
System leakage capacitance measured value range
R
F
> 20 kΩ ........................................................................ 0…200 μF
Operating uncertainty ......................................................................................................................... ±15 %, at least ±2 μF
Password ................................................................................................................................................ off/0…999 (0, off)*
Fault memory alarm messages ................................................................................................................................ on/(off)*
ISOMETER isoHV525-M4-4:
Insulation resistance measured value range (
R
F
).............................................................................................. 1 kΩ…4 MΩ
Operating uncertainty ........................................................................................................................ ±15 %, at least ±3 kΩ
Serial interface (valid for isoHV525-S4-4 devices only)
Interface/protocol........................................................................................................... RS-485/BMS, Modbus RTU, isoData
Baud rate ......................................................................BMS (9.6 kbit/s), Modbus RTU (selectable), isoData (115.2 kbits/s)
Cable length (9.6 kbits/s) ....................................................................................................................................... ≤ 1200 m
Cable: twisted pairs, shield connected to PE on one side ...................................................................... min. J-Y(St)Y 2x0.6
Terminating resistor .......................................................................................... 120 Ω (0.25 W), internal, can be connected
Device address, BMS bus, Modbus RTU .............................................................................................................. 3…90 (3)*
Analogue output (valid for isoHV525-M4-4 only)
Operating mode............................................................................................................................................ Mid-scale 120 kΩ
Functions......................................................................................................................................................... Insulation value
Voltage......................................................................................................................................................0…10 V (≥ 20 kΩ)
Tolerance ....................................................................................................................... ±10 %, +2 % of the full scale value
Switching elements
Switching elements ................................................................................................ 2 x 1 N/O contact, common terminal 11
Operating principle ......................................................................................N/C operation/N/O operation (N/O operation)*
Electrical endurance, number of cycles ........................................................................................................................ 10,000
Contact data acc. to IEC 60947-5-1:
Utilisation category................................................................................................. AC-12...AC-14... DC-12... DC-12... DC-12
Rated operational voltage ......................................................................................230 V.....230 V......24 V.....110 V.....220 V
Rated operational current ......................................................................................5 A.........2 A........1 A..... 0.2 A..... 0.1 A
Minimum contact rating .................................................................................................................... 1 mA at AC/DC
≥
10 V
Environment/EMC
EMC .......................................................................................................................................... IEC 61326-2-4, EN 50121-3-2
Ambient temperatures:
Operation:
(
U
n
< 700)....................................................................................................................................... -55…+70 ºC
(
U
n
> 700)....................................................................................................................................... -55…+55 ºC
Transport .......................................................................................................................................................... -55…+85 ºC