ISOMETER® Modbus register assignment
35
isoHV525_D00297_04_M_XXEN/05.2018
Register
Property
Description
Format
Unit
Value range
3000
RW
Reserved
---
---
---
3001
RW
Reserved
---
---
---
3002
RW
Reserved
---
---
---
3003
RW
Reserved
---
---
---
3004
RW
Reserved
---
---
---
3005
RW
Pre-alarm value resist-
ance measurement
"R1"
UINT 16
kΩ
R2 … 500
3006
RW
Reserved
---
---
---
3007
RW
Alarm value resist-
ance measurement
"R2"
UINT 16
kΩ
10 … R1
3008
RW
Activation alarm value
undervoltage "U<"
UINT 16
---
0 = Inactive
1 = Active
3009
RW
Alarm value under-
voltage "U<"
UINT 16
V
30 … U>
3010
RW
Activation alarm value
overvoltage "U>"
UINT 16
---
0 = Inactive
1 = Active
3011
RW
Alarm value
Overvoltage "U >"
UINT 16
1/10 V
U< … 1100
3012
RW
Memory function for
alarm messages
(Fault memory) "M"
UINT 16
---
0 = Inactive
1 = Active
3013
RW
Operating mode of
relay 1 "r1"
UINT 16
---
0 = n.o.
1 = n.c.
3014
RW
Operating mode of
relay 2 "r2"
UINT 16
---
0 = n.o.
1 = n.c.
3015
RW
Bus address "Adr"
UINT 16
---
0 / 3 … 90
3016
RW
Baud rate "Adr 1"
UINT 16
---
0 = BMS
1 = 1.2 k
2 = 2.4 k
3 = 4.8 k
4 = 9.6 k
5 = 19.2 k
6 = 38.4 k
7 = 57.6 k
8 = 115.2 k