ISOMETER® Modbus register assignment
42
isoHV525_D00297_04_M_XXEN/05.2018
To convert parameter data, data type descriptions are required. Text representation is
not necessary in this case.
Value
Description of parameters
1023 (0x3FF)
Parameter/measured value invalid.
The menu item of this parameter is not displayed.
1022 (0x3FE)
No measured value/no message
1021 (0x3FD)
Measured value/parameter inactive
1020 (0x3FC)
Measured value/parameter only temporarily inactive (e.g. while trans-
mitting a new parameter). Indication in the menu "…".
1019 (0x3FB)
Parameter/measured value (value) unit not displayed
1018 (0x3FA)
Parameter (code selection menu) unit not displayed
1017 (0x3F9)
String max. 18 characters (e.g. device type, device variant, …)
1016 (0x3F8)
1015 (0x3F7)
Time
1014 (0x3F6)
Date: Day
1013 (0x3F5)
Date: Month
1012 (0x3F4)
Date: Year
1011 (0x3F3)
Register address (unit not displayed)
1010 (0x3F2)
Time
1009 (0x3F1)
Factor multiplication [*]
1008 (0x3F0)
Factor division [/]
1007 (0x3EF)
Baud rate
1022 (0x3FE)
1023 (0x3FF)
Invalid