![Bender ISOMETER isoHV525 Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/bender/isometer-isohv525/isometer-isohv525_manual_2731666043.webp)
43
isoHV525_D00297_04_M_XXEN/05.2018
9. IsoData data string
In IsoData mode, the ISOMETER® continuously sends the entire data string with a cycle
time of approximately 1 second. Communication with the ISOMETER® in this mode is
not possible and no additional sender may be connected to the RS-485 bus cable.
IsoData is activated by setting Adr = 0. The IsoData protocol can only be terminated by
sending the command "Adr3" during an interval of the isoHV525-S4-4.
String
Description
!;
Start symbol
v;
Insulation fault location ' ' / '+' / '-'
1234, 5;
Insulation resistance
R
F
[kΩ]
1234;
System leakage capacitance
C
e
[μF]
1234, 5;
Reserved
+1234;
Nominal system voltage
U
n
[V
RMS
]
Nominal system voltage type: AC or unknown: ' ' DC: '+' / '-'
+1234;
Residual voltage
U
L1e
[V
DC
]
+1234;
Residual voltage
U
L2e
[V
DC
]
+123;
Insulation fault location -100 … +100 [%]
1234, 5;
Approximate asymmetrical insulation resistance
R
UGe
[kΩ]
1234;
Alarm message [Hexadezimal] (without leading „0x“)
The alarms are included in this value with the OR function.
Assignment of the alarms:
0x0002 Device fault
0x0004 Prewarning insulation resistance
R
F
an
L1/+
0x0008 Prewarning insulation resistance
R
F
an L2/-
0x0010 Alarm insulation resistance
R
F
an L1/+
0x0020 Alarm insulation resistance d
R
F
an L2/-
0x0030 Alarm insulation resistance
R
F
symmetrical
0x0040 Alarm undervolatge
U
n
0x0080 Alarm overvoltage
U
n
0x0100 System test message
0x0200 Device start with alarm
1
Update counter, consecutively counts from 0 to 9.
It increases with the update of the insulation resistance value.
<CR><LF>
End of string
Содержание ISOMETER isoHV525
Страница 49: ...Technical data 49 isoHV525_D00297_04_M_XXEN 05 2018 ...
Страница 51: ......