![Bender ISOMETER isoHV525 Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/bender/isometer-isohv525/isometer-isohv525_manual_2731666016.webp)
Function
16
isoHV525_D00297_04_M_XXEN/05.2018
The partial resistances can be calculated from the total insulation resistance
R
F
and the
faulty conductor (R %) using the following formula:
Fault on conductor L1/+ ->
R
L1F
= (200 % *
R
F
)/(100 % + R %)
Fault on conductor L2/- ->
R
L2F
= (200 % *
R
F
)/(100 % – R %)
If the values
R
F
or
U
n
exceeds the set response values, this will be indicated by the relays
"K1" and "K2". In addition, the operation of the relay (n.c./n.o.) can be set and the fault
memory "M", activated. If the values
R
F
or
U
n
exceed their release value (response value
plus hysteresis) uninterrupted for no longer than the period
t
off
, then the alarm relays
will switch back to their initial position. If the fault memory is enabled, the alarm relays
remain in the alarm state until the external Test/Reset button is pressed or until the sup-
ply voltage
U
s
is switched off. The device function can be tested using the Test/Reset
button. Device parameters are initially assigned by Bender. Parameterisation of the ISO-
METER
isoHV525-S4-4 is also possible via the BMS bus, for example by means of a BMS-
Ethernet gateway (COM465IP) or Modbus RTU
.
3.2.2.1
Manual self test
The integrated self test function tests the function of the insulation monitoring device
and the connection to IT system to be monitored. A self test is started by pressing the
external test/reset button. Relay 1 ("K1") is switched during a manual self test. In the
event of a fault, relay 2 ("K2") switches and the measuring function is interrupted.
Internal device errors can be caused by external disturbances or internal hardware er-
rors. After eliminating the fault, the alarm relays are automatically reset or are reset to
the initial position by pressing the Test/Reset
button. The self test can take a few minu-
tes.
The isoHV525 determines the system leakage capacitance via an
impedance measurement whose frequency is adjusted to the most
accurate insulation measurement. The measurement signal is influenced
by rectifiers or inverters, and can lead to phase errors which in turn can
lead to a distorted system leakage capacitance value.
Содержание ISOMETER isoHV525
Страница 49: ...Technical data 49 isoHV525_D00297_04_M_XXEN 05 2018 ...
Страница 51: ......