Function
14
isoHV525_D00297_04_M_XXEN/05.2018
3.1.2.6
Analogue output
The isoHV-M4-4 ISOMETER® outputs and analogue voltage in the range 0. . .10 V
.
Calculation of the insulation resistance using the analogue output:
Activation
Setting
Description
FAC
U 0 . . . 10 V
0 . . . 10 V, Permissible load > 20 kΩ
on
120 kΩ
The scaled reference value for thr displayed non-
linear resistance at 50% of interface control..
Variable
Description
R
F
Insulation fault in kΩ
R
SKM
Scaled reference value in kΩ (i.e. 120 kΩ)
A
1
Upper analogue output value (i.e. 10 V)
A
2
Measured analogue output value
The analog output provides stable output values only after the
isoHV525-M4-4 has been initialized.
A₁ x R
SKM
(kΩ)
A
R
F
(kΩ) =
- R
SKM
(kΩ)