![Bender ISOMETER isoHV525 Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/bender/isometer-isohv525/isometer-isohv525_manual_2731666032.webp)
Data access to the isoHV525-S4-4 using the Modbus RTU protocol
32
isoHV525_D00297_04_M_XXEN/05.2018
7.2 Writing to the Modbus register (parameter setting)
Registers in the device can be modified with the Modbus command 0x10 (set multiple
registers). Parameter registers are available from address 3000. The content of the regis-
ter is listed in the table
7.2.1
Master device sends a command to the ISOMETER®
In this example, the Master addresses the ISOMETER® with address 3 and requests that
the content of the register with address 3003 is set to 2.
7.2.2
The ISOMETER®s answers the Master
Byte Name Example
Byte 0
ISOMETER® Modbus address
0x03
Byte 1
Function code
0x10
Byte 2, 3
Start register
0x0BBB
Byte 4, 5
Number of registers
0x0001
Byte 6
Number of data bytes
0x02
Byte 7, 8
Data
0x0002
Byte 9, 10
CRC16 checksum
0x9F7A
Byte Name Example
Byte 0
ISOMETER® Modbus address
0x03
Byte 1
Function code
0x10
Byte 2, 3
Start register
0x0BBB
Byte 4, 5
Number of Registers
0x0001
Byte 6, 7
CRC16 checksum
0x722A