Installation, connection and commissioning
23
isoHV525_D00297_04_M_XXEN/05.2018
For details about the conductor cross sections required for wiring, refer to the technical
data from
Legend to the wiring diagram for isoHV525-M4-4:
The lower temperature range applies only when the cable is firmly laid or
installed.
Wire number
Terminal
Connection
1
2
A1
A2
Connection to the supply voltage
U
s
via fuses (line protec-
tion):
If supplied from an IT system, both lines have to be protected
by a fuse.
3 and 4
5
E
KE
Connect each terminal separately to PE.
6
T/R
Connection for the external combined Test/Reset button
7
8
M-
M+
Analogue communication interface
9
10
11
11
14
24
Common connection for
"
K1
"
und
"
K2
"
Connection to alarm relay
"
K1
"
Connection to alarm relay
"
K2
"
Red
Blue
L1/+
L2/-
Connection to the IT system to be monitored