19
5. Installation
5.1 Basic configuration
5.1.1
Preparations
First consult the person in charge of the electrical installation for the addresses and net masks
of the protocol converter in the respective bus structures (BMS and TCP/IP). It is also nec-
essary to find out whether the FTC470XET can be operated as BMS master (default setting
for higher data throughput).
Prior to installation and connection, an address has to be assigned to the FTC470XET. What
you need is:
z
A free BMS address between 2 and 30 for FTC470XET or a permission to assign the master function to
the device, that means, BMS address 1 is assigned to the FTC470XET.
z
A free IP address and the net mask for the FTC470XET connection to the local network intended to
be used, subnetting is possible.
z
Optional:
The IP address of the default gateways, DNS server, and WINS server
z
A cross-over-patch cable and a straight-through-patch cable (LAN cable).
A cross-over-patch cable can be distinguished from a straight-through-patch cable by the wiring of
the transparent RJ45 plugs. The sequence of colours of the parallel conductors is different.
z
A PC or Laptop which at least can be operated temporarily separately from the computer network.
5.1.2
Setting the BMS address
1. If it is possible from the technical point of view to assign the master function on the BMS bus to the
FTC470XET, BMS address 1 must be used. The device will already be delivered with this factory set-
ting.
2. Otherwise set the appropriate BMS address (2 to 30, see page 15) by means of the DIP switch accord-
ing to the binary system. By way of example, address 5 corresponds to the switch positions:
A4=0 A3=0 A2=1 A1=0 A0=1
Factory setting = 1 (BMS master)
If you are familiar with the configuration of computer networks, you can carry out
the connection of the FTC470XET by yourself.
Otherwise please contact your EDP
administrator!
A
ssigning addresses that are already used by existing devices on the BMS or TCP/IP
network can cause serious malfunctions.
Содержание FTC470XET
Страница 10: ...Safety instructions 10 TGH1375en 02 2010...
Страница 18: ...The FTC470XET protocol converter 18 TGH1375en 02 2010...
Страница 56: ...Web server application examples 56 TGH1375en 02 2010...
Страница 78: ...Technical data 78 TGH1375en 02 2010...
Страница 80: ...Frequently asked questions 80 TGH1375en 02 2010...
Страница 83: ......