Web server application examples
52
7.2.6
Changing an alarm text or a measuring point description
In some cases it may be useful to adapt an alarm text to the special local requirements. For
example, if there is the requirement that an RCMS470-12 with BMS address 5 should display
the message "Undercurrent" in case of undercurrent on channel 4. In addition, a description
of the location of the mounted CT should be displayed.
1. Select: "Address 5: RCMS470-12“ from the main menu. The required setting submenu will appear.
2. Click on "System description". A list will appear where you can type in an alarm text and a description
of the measuring point for each channel.
3. Type "Undercurrent" as new alarm text into the "Type" column and "V0.27“ into the "Measuring
point" column. Confirm your actions with the "Save" button.
4. After calling up the "Current values" menu item, the measuring results and the associated new terms
are displayed.
Submenu item: Enter system description
Channel 1 to 12:
Measuring point
- Description of location(V0.27)
Alarm text
- Description of alarm (undercurrent)