9.7 LEDs
9 Technical Data
Info 1: With inductive loads of consumption category DC13 (EN60947-5-1), the outputs can connect
currents of 1.6 A at a frequency of 1 Hz.
Info 2: Technically possible and approved under the following conditions:
D
Looped sensor/system power supply max. 2.5 A
D
Power supply cable STL 204 (5 x 1.0 mm
2
)
D
Ambient temperature max. 40° C / 104° F
Table 36: Information on the outputs
9.7 LEDs
U
S
Green
System/sensor power supply, voltage level
18 V <= U
S
+/- 1 V <=30 V
Red
System/sensor power supply, voltage level
U
S
< 18 V +/- 1 V or U
S
> 30 V +/- 1 V
Off
No system/sensor power supply
U
L
Green
Actuator power supply, voltage level
18 V <= U
L
+/- 1 V <=30 V
Red
Actuator power supply, voltage level
U
L
< 18 V +/- 1 V or U
L
> 30 V +/- 1 V
Off
No actuator power supply
X1…X8 A
Yellow
Channel status A "On"
DIA
Red
Periphery error (sensor or actuator overload/short-circuit)
Off
Not connected, status "Off", no error
X1…X8 B
White
Channel status B "On"
Red
Periphery error (actuator overload/short-circuit)
Off
Not connected, status "Off", no error
P1 Lnk/Act Green
Ethernet connection exists to another subscriber. Link connection created.
P2 Lnk/Act Flashing
yellow
Data exchange with another subscriber.
Off
No connection to another subscriber. No link, no data exchange.
BF
Red
No configuration, no or slow physical connection
Technical Manual LioN-P PROFINET
Version 2.0 10/2017
74