5.2 Configuration of LioN-P
PROFINET Modules in TIA Portal
5 Configuration and Startup
The input and output addresses specified in the device summary can be
changed.
LioN-P 16DIO modules (0980-ESL-300-111, 0980-ESL-300-121, 0980-
ESL-390-111, 0980-ESL-390-121, 0980-ESL-390-121-DCU1) have an
extended I/O function scope. Different profiles (e.g. 16 DI/DO) or modules
may be used in slot 1 of the subrack.
The advantage of this is that all older inventories of digital I/O modules can
be replaced in each instance by a LioN-P 16DIO module. The selection of
a suitable profile and the use of IO mapping in the module parameters can
be replaced without changing the I/O addresses in the PLC program of these
devices.
To change a profile it is necessary to delete the module in slot 1 and to insert
another one in its place. This is done by adding a LioN-P PROFINET module
through the hardware catalog.
The following module profiles (e.g. 16DI/DO) are available for configuration
of a LioN-P 16DIO module:
5.2.1 Assigning a Unique Device Name
PROFINET IO devices in the PROFINET network are activated through a
unique device name. This can be freely assigned by the user, but may only
be used once on the network.
In the device summary of the LioN-P module, select slot 0 and in
General
issue a suitable module name.
Technical Manual LioN-P PROFINET
Version 2.0 10/2017
26