5.2 Configuration of LioN-P
PROFINET Modules in TIA Portal
5 Configuration and Startup
General Parameters
Report Alarms:
Activate/deactivate Global PROFINET alarm messages.
Report Alarm U
L
:
Activate/deactivate PROFINET alarm message for missing actuator supply voltage (U
L
). If the global
PROFINET alarm messages are deactivated, this alarm is not registered.
Report Alarm DO without U
L
:
Activate/deactivate PROFINET alarm message for missing actuator supply voltage (U
L
) and actuation
of an actuator. If the global PROFINET alarm messages are deactivated, this alarm is not registered.
Force Mode:
Permit/inhibit use of Force Mode on web server.
Web interface:
Permit/inhibit use of web server.
DCU Startup (for DCU modules only):
Deactivate/block DCU function or start DCU program. Further details are available in the μDCU
Manual.
Digital Out Restart Mode:
Automatic restart following short circuit of digital output or reset of channel diagnosis when resetting
digital output
Fail Safe Configuration
These parameters are provided to all module types with digital outputs. If a
breakdown/loss of PROFINET communication occurs or another major fault,
the outputs can be switched using parameterization into a reliable condition.
Technical Manual LioN-P PROFINET
Version 2.0 10/2017
32