Technical data
Technical manual LioN-Link BusHead EtherNet/IP™
Release 1.1 04/2016
9.4 LEDs
63
MS
Green
Device ready for operation
Flashing green
Device is not configured, or incorrect
configuration
Flashing red
Firmware update
Flashing red/green
Device is performing a self-test
off
Device off
NS
Green
Connected to a master
Flashing green
IP address exists, but no connection to a master
Red
IP address occupied by another device
Flashing red
Connection timeout
off
Device off
S1
Green
Line 1 active, data exchange with I/O modules
Red
Incorrect configuration, or wrong module
Alternately flashing red/green Restart line 1
S2
Green
Line 2 active, data exchange with I/O modules
Red
Incorrect configuration, or wrong module
Alternately flashing red/green Restart line 2
Us1
Green
System/sensor power supply line 1 present
off
System/sensor power supply line 1 missing
Us2
Green
System/sensor power supply line 2 present
off
System/sensor power supply line 2 missing
Table 22: Information on the LED colors
Содержание 934 815-001
Страница 2: ...2 Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 6: ...Contents 6 Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 10: ...About this manual 6 1 3 Version information Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 18: ...System description 14 3 2 Product overview Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 28: ...Assembly and wiring 24 4 4 Port assignments Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 32: ...Starting operation 28 5 3 IP address Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 68: ...Technical data 64 9 4 LEDs Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 70: ...Declaration of conformity 66 Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...